background image

SyxthSense Ltd

Copyright © 2020 SyxthSense Ltd. All rights reserved - 11/2020 

PS 

CT2.161

 - 8/34

Online store: 

www.syxthsense.com

Enquiries: T:

  +44 (0)1392 875 414   

E:

 [email protected]

One/Two Stage Heating Control

One/Two Stage Cooling Control

One/Two Stage Heating and One/Two Stage Cooling Control (up to three outputs)

One Stage Heating/Cooling Control (Change-Over)

The controller modulates the heating and cooling demand outputs according to the calculated setpoint  
and the current temperature. The control can be either P-control or PI-control. The calculated setpoint 
consists sum of Nominal Setpoint (nSP) and the user setpoint adjustment (SPA). 

As default for SRC-700/701, heating stage 1 output is linked to Y2 for modulating 0..10Vdc control, 
cooling stage 1 is linked to analogue output Y3. With SRC-702/704H, heating stage 1 is linked to DO1 
PWM control and cooling stage 1 is linked to DO2 PWM control. 

It is possible to set the control loop outputs to direct/reverse, which reverses the control output (valve) 
running direction (valve drives from 100% to 0%). This can be configured individually for each stage in 
the Configuration Parameters.

CONTROL

 OUTPUT

HEATING

STAGE 1

COOLING

STAGE 1

calcSP

SRC600/601/602 - 0..10Vdc

SRC602 - PWM

SRC600/601/602 - 0..10Vdc

SRC602 - PWM

HDz

MEASURED 
TEMPERATURE

100%

0%

+

-

COOLING

STAGE 2

SRC600/601/602 - 0..10Vdc

HEATING

STAGE 2

NOTE: SRC600 has maximum of 3 x 0-10Vdc outputs
NOTE: SRC601 has maximum of 2 x 0-10Vdc outputs
NOTE: SRC602 has maximum of 2 x PWM 24V outputs and 1 x 0-10Vdc outputs.

ECO Deadzone

fSP

2°C /

3.6°F

fSP = Frost Setpoint

SRC600/601/602 - 0..10Vdc

HDz = COMFORT Heating Deadzone

CDz

CDz = COMFORT Cooling Deadzone

eHDz

eCDz

calcSP = Calculated Setpoint

Between heating and cooling stage 1 is a ’deadzone’. With P-control in the ’deadzone’ the cooling and 
heating loop demand is 0%. With PI-control, if the temperature remains in the ’deadzone’ for a 
prolonged period, the heating/cooling demand ramps to 0%. The ’deadzone’ allows the temperature to 
fluctuate around the setpoint without heating or cooling valves starting to open. The SRC has a built-in 
lock that prevents cooling and heating demands to be on simultaneously. 

The ’deadzone’ has an individual settings (HDz and CDz) for both heating and cooling side allowing 
asymmetrical setting. E.g. in some cases it is important that the cooling starts to respond faster than 
heating when the temperature deviates away from the setpoint.

Note: Conceptually calcSP - HDz is effective Heating Setpoint and  CDz is Effective Cooling 
Setpoint. For the user it is easier to set and display a single setpoint and the ’deadzone’ limits are set 
during the commissioning to provide effective heating and cooling setpoints..

The target temperature is typically adjusted by the user by pressing UP & DOWN buttons. The target 
temperature/deadzone is changed in different operating situations as follows; 

COMFORT MODE; target temperature as adjusted by the user (or via the networked system) 
and displayed on the screen. The calculated target setpoint (calcSP) consist of the Nominal Set-
point plus the user adjustment (SPA) set via the screen. The user setpoint adjustment is limited 
by the Setpoint Adjust Max/Min settings (as d/-3°).

ECO MODE; target Nominal Setpoint remains the same.The user adjustment (SPA) is disabled 
and the ’deadzone’ settings are expanded to Night Heating Deadzone and Night Cooling Dead-
zone.

OFF MODE; the device controls to Frost Setpoint (fSP). The user adjustment (SPA) is disabled.

NOTE:If activated, the High/low Limit Control shifts the effective target temperature (calculated 
setpoint) as required.

Heating / Cooling 
Change-Over

The main temperature control loop heating stage 1 and cooling stage 1 can be forced to operate in 
heating or cooling mode using the change-over function. The change-over is carried out using digital 
input, temperature measurement or over the network. This allows the same pipe works to be used for 
both heating and cooling in different seasons.

The change-over function is activated if it is selected for the DI1/RI1/RI2. 

With digital input the change-over is activated when the input is activated. Over the network the 
change-over can be activated by setting the change-over parameter on.

Summary of Contents for SRC-P-700 Series

Page 1: ...ic Summer Winter Time Change Over Product sheet CT2 161 Type SRC P 700 Product Selection Table 1 2 3 4 5 6 1 Device type Touchscreen Room Controller 2RI 1DI 3AO htg clg fan Schedule SRC P 700 Touchscr...

Page 2: ...maximum 63 devices MAC Addressing 0 127 via Touchscreen Device ID Default 651000 MAC Address Adjustable Communication 9k6 19k2 38k4 57k6 76k8 Baud Parity None Even Odd 1 or 2 Stop Bits adjustable thr...

Page 3: ...ommon RI1 Remote NTC10 Temperature Sensor Input 1 0 10V with AI option RI2 Remote NTC10 Temperature Sensor Input 2 0 10V with AI option Din Volt Free Digital Input Contact dry contact 485A Modbus BACn...

Page 4: ...nput 1 0 10V with AI option RI2 Remote NTC10 Temperature Sensor Input 2 0 10V with AI option Din Volt Free Digital Input Contact dry contact 485A Modbus BACnet MS TP RS485 A Connection 485B Modbus BAC...

Page 5: ...n Speed 1 On Off Valve RCOM Relay Common RLY2 230V 7A Relay Fan Speed 2 RLY3 230V 7A Relay Fan Speed 3 TR2 24Vac 1A Triac switched to 0V default Cooling PWM 24V 24Vac dc Supply G0 0V Common TR1 24Vac...

Page 6: ...Ring modulates based on how far from the Effective Heating Cooling Setpoint the temperature is When the difference is 2 C 3 6 F the Energy Ring is at full density calcSP HDz MEASURED TEMPERATURE CDz...

Page 7: ...in the stand by level switches the backlight OFF The screen backlight is automatically activated when it is touched Further Settings and Information The FURTHER SETTINGS screen shows additional user...

Page 8: ...re to fluctuate around the setpoint without heating or cooling valves starting to open The SRC has a built in lock that prevents cooling and heating demands to be on simultaneously The deadzone has an...

Page 9: ...target setpoint on the display is not changed during the limitation The limit icon indicates active limitation To see the effective limited setpoint enter Controller Status and Information display Not...

Page 10: ...C 6 0 0 6 0 1 6 0 2 0 1 0 V d c S R C 6 0 2 P W M Note If the 7 Day Schedule has been activated the device starts to use the operating mode set at the next switching point e g if the next switching p...

Page 11: ...chedule point regardless of the Boost Time or Current Measurement Please note that at the next switching time the target COMFORT ECO OFF BOOST must be different from the target in the current period i...

Page 12: ...O MATIC CONTROL 6 SPEED MANUAL FAN CONTROL M 17 33 0 50 67 83 100 A Auto SPEED SET BY CONTROLLER 100 0 50 100 0 33 67 0 100 M M M M M M M M M M M M A Auto SPEED SET BY CONTROLLER A Auto SPEED SET BY C...

Page 13: ...e actuators 100 CONTROL OUTPUT D e h u m i d i f i c a t i o n SP Setpoint e g 50 rH 100 Proportional Band e g 5 rH SP 0 Humidity rH 0 rH 100 rH LOOP OUTPUT H u m i d i f i c a t i o n 0 instead of 0...

Page 14: ...to open the operating mode does not change until the countdown timer has expired DIGITAL INPUT DELAY setting Note Resistive Inputs as a Digital Input operate with approx ten seconds delay and are not...

Page 15: ...apter 6 PORT REVERSE see 6 PORT VALVE control chapter reverse operation Analogue Output Scaling Output Limitation Each of the analogue outputs Y1 Y2 Y3 can have Output minimum voltage percentage Outpu...

Page 16: ...The SRC 700 controller can be configured to control Belimo 6 Port valve by selecting 6 Port or 6 Port Reverse mode for the analogue output Y1 Y2 Y3 The diagram below illustrates the operation Note Ana...

Page 17: ...ensor 2 Fault The typical alarm reasons are External sensor 1 Res1 fault when activated out of range External sensor 2 Res1 fault when activated out of range Built in sensor fault Digital Input Alarm...

Page 18: ...of the temperature control loop Set to 0 to disable 0 1 200 seconds Default 600s Heating Stages Number of Heating Stages 0 None 1 1 Stage Default 2 2 Stages Heating Stage 1 Dir Heating Stage 1 Directi...

Page 19: ...setting Disabled This is done by entering and exiting the System configuration menu Humidity Display Enable Disable Humidity Display if option fitted 0 Disabled 1 Enabled default Digital Input Mode Di...

Page 20: ...fault Anti JAM Valve Exercise 0 14 Days default 0 disabled PWM Period PWM Period SRC 702 SRC 704H 0 120 Seconds default 30 INPUTS OUTPUTS Parameter Name Description Range FAN BOOST TIMES Parameter Nam...

Page 21: ...ACnet Baud Rate 0 9600 Default 1 19200 2 38400 3 57600 4 76800 Parity Only Modbus BACnet versions Parity 0 None Default 1 Odd 2 Even Stop Bits Only Modbus BACnet versions Stop Bits 0 1 Stop Bit Defaul...

Page 22: ...gister Parameter Description Data Type Raw Data Range FUNCTION CODE 01 READ COILS FUNCTION CODE 05 WRITE SINGLE COIL FUNCTION CODE 15 WRITE MULTIPLE COILS 100 OFF Mode Override 0 1 Off On 101 ECO Mode...

Page 23: ...ge Default 2 2 Stages 111 Heating Stage 1 Direction Unsigned 16 0 1 0 Reverse Default 1 Direct 112 Heating Stage 2 Direction Unsigned 16 0 1 0 Reverse Default 1 Direct 113 Number of Cooling Stages Uns...

Page 24: ...put Y2 Override Value Unsigned 16 0 1000 0 100 0 10 0V Default 0 136 Analogue Output Y3 Override Value Unsigned 16 0 1000 0 100 0 10 0V Default 0 137 Y1 Minimum Output Unsigned 16 0 1000 0 100 0 Defau...

Page 25: ...Unsigned 16 0 4 0 Lock mode disabled default 1 On Off workable only 2 Temp settings only available 3 All buttons disabled 156 Lock Mode Password Unsigned 16 0 9999 0000 9999 157 Boost Time Unsigned 16...

Page 26: ...ride Level 1 100 On Off 50 3 Levels 33 4 Levels 3 Override Level 2 100 3 Levels 66 4 Levels 4 Override Level 3 100 4 Levels 178 Override Blinds Notes After overriding the level the parameter returns t...

Page 27: ...gned 16 0 2400 0 2400 Default 2200 215 Tuesday Switching Time 1 Target Unsigned 16 0 3 0 Comfort Default 1 ECO 2 Off 3 Boost 216 Tuesday Switching Time 2 Target Unsigned 16 0 3 217 Tuesday Switching T...

Page 28: ...0 2400 0 2400 Default 0600 261 Sunday Switching Time 2 Unsigned 16 0 2400 0 2400 Default 1000 262 Sunday Switching Time 3 Unsigned 16 0 2400 0 2400 Default 1300 263 Sunday Switching Time 4 Unsigned 16...

Page 29: ...ue Please note AV1 AV10 are Read Only 31 AV 0 Built In Sensor Read Only2 AV 1 RI_1 RI1 Temperature AI1 R O2 AV 2 RI_2 RI2 Temperature AI2 R O2 AV 3 Target Calculated Setpoint R O2 AV 4 Humidity Read O...

Page 30: ...ry Properties 40106 Setpoint Adjust Minimum REAL 20 0 0 0 C F Default 3 0 40107 Setpoint Adjust Maximum REAL 0 0 20 0 C F Default 3 0 40110 Number of Heating Stages Unsigned 0 None 1 1 Stage Default 2...

Page 31: ...ult Cooling Stage 1 Unsigned 40143 Anti JAM Time out Unsigned 0 14 Days 0 Disabled Default 40144 RI1 Mode Unsigned 0 Disabled default 1 Room NTC10 Control 2 Floor NTC10 High Low Lim 3 Aux Loop 4 Netwo...

Page 32: ...midity Unsigned 0 Disabled 1 Enabled default 40165 Show Swap Temperature Units Icon Unsigned 0 Disabled default 1 Enabled 40166 Zone 1 Room Sensor Text Unsigned 1 Room Default 2 Floor 3 Outside 4 Zone...

Page 33: ...seconds Default 0 0 Infinite Delay 40190 Aux Heating Loop Proportional Band Unsigned 1 0 50 0 C F Default 4 C 40191 Aux Heating Loop Control Integral Action Unsigned 0 1 200 seconds Default 600 40192...

Page 34: ...61 34 34 Online store www syxthsense com Enquiries T 44 0 1392 875 414 E info syxthsense com Dimensions 88mm 3 46 14 5mm 0 56 52mm 2 05 43mm 1 69 112mm 4 41 88mm 3 46 52mm 2 05 112mm 4 41 53mm 2 09 49...

Reviews: