SyxthSense Ltd
Copyright © 2020 SyxthSense Ltd. All rights reserved - 11/2020
PS
CT2.161
- 32/34
Online store:
www.syxthsense.com
Enquiries: T:
+44 (0)1392 875 414
E:
Optional
Properties
None
Property Name /ID
Attributes
Range
Default
Property ID
Description
BACnet Data Type
Range
Proprietary
Properties
40155
Lock Mode
Unsigned
0 = Lock mode disabled (default)
1 = On/Off workable only
2 = Temp settings only available
3 = All buttons disabled
40156
Lock Mode Password
REAL
0000...9999
40157
Boost Time
Unsigned
0 = Permanent (Default 0)
1..480 minutes
40158
Boost Target
Unsigned
0 = Nominal SP (Temperature)
1 = CO2 SP
2 = Humidity SP
3 = Dehum SP
4 = Fan Demand
5 = Aux. Temp SP
40159
Boost Target Value
Unsigned
0 ..5000 (default 25)
40164
Display Humidity
Unsigned
0 = Disabled
1 = Enabled (default)
40165
Show Swap Temperature Units
Icon
Unsigned
0 = Disabled (default)
1 = Enabled
40166
Zone 1 Room Sensor Text
Unsigned
1 = Room (Default)
2 = Floor
3 = Outside
4 = Zone 1
5 = Zone 2
6 = Zone 3
7 = Bathroom
8 = Sauna
9 = Bedroom
10 = Kitchen
11 = Cooler
12 = Flow
13 = Hot Water
14 = Tank
15 = Pool
16 = Cabin
40167
Zone 2 Floor Sensor Text
Default: 2 = Floor
Unsigned
0 = Disabled
1 = Room
2 = Floor
3 = Outside
4 = Zone 1
5 = Zone 2
6 = Zone 3
7 = Bathroom
8 = Sauna
9 = Bedroom
10 = Kitchen
11 = Cooler
12 = Flow
13 = Hot Water
14 = Tank
15 = Pool
16 = Cabin
40168
Zone 3 Outside Sensor Text
Default: 3 = Outside
Unsigned
40169
Alarm 1 Source
Unsigned
0 = CO2
1 = Room (Temperature)
2 = Humidity
3 = None (Default)
40170
Alarm 1 Amber Switching Point
Unsigned
0..5000 (Default 0)
40171
Alarm 1 Red Switching Point
Unsigned
0..5000 (Default 0)
40172
Alarm 1 Hysteresis
Unsigned
0..5000 (Default 0)
40173
Alarm 2 Source
Unsigned
0 = CO2
1 = Room (Temperature)
2 = Humidity
3 = None (Default)