CONDENSATION - when the digital input is closed the cooling loops are set to 0% to prevent 
condensation happening. In this mode digital input is typically connected to a condensation sensor.

CONTACT ALARM - when the contact closes the "DI Contact Alarm" alarm message is displayed on 
the screen.

NETWORK; the digital input is used for network monitoring purposes. 

CLOSE/OPEN FOR BOOST - when digital input activates the controller operates in Boost mode, until 
the digital input de-activates (only with CE-option). With the digital input boost the ’Target’ text is 
replaced by ’Boost’ text.

Note: Digital Input Delay Timer parameter applies to all settings. 

Analogue Outputs 

The controller has three analogue 0-10Vdc outputs that are typically linked to the control loop outputs. 
The following list states the possible options:

NETWORK; As a network 0-10Vdc output variable 

HEATING STAGE 1; 0-10Vdc output is linked to Heating Stage 1

HEATING STAGE 2; 0-10Vdc output is linked to Heating Stage 2

COOLING STAGE 1; 0-10Vdc output is linked to Cooling Stage 1

COOLING STAGE 2; 0-10Vdc output is linked to Cooling Stage 2

EC FAN; 0-10Vdc output is linked to Fan Control Loop Output

CO2; 0-10Vdc output is linked to CO2 Control Loop Output (CO2 Models)

MAXIMUM VAV; 0-10Vdc linked to maximum of the Cooling stage 1 and CO2 loops 

MAXIMUM FAN; 0-10Vdc linked to maximum of the CO2 loop and fan loop

HUMIDIFICATION; 0-10Vdc output is linked to Humidity Control Loop Output (RH Models)

DE-HUMIDIFICATION; 0-10Vdc output is linked to De-Humidity Control Loop Output (RH Mod-
els)

AMBER/RED; 0-10dc is @ 50% when Amber or Red alarm is active

RED; 0-10Vdc is @ 100% when Red alarm is active

HEATING STAGE 1 STAT; see RELAY OUTPUT / ON-OFF control chapter

COOLING STAGE 1 STAT; see RELAY OUTPUT / ON-OFF control chapter

FAN STAT; see RELAY OUTPUT / ON-OFF control chapter

AUX LOOP; see AUXILIARY HEATING CONTROL LOOP  chapter

6-PORT; see 6-PORT VALVE control chapter

6-PORT REVERSE; see 6-PORT VALVE control chapter (reverse operation)

Analogue Output Scaling / 
Output Limitation

Each of the analogue outputs (Y1,Y2,Y3) can have 

Output minimum voltage (percentage)

Output maximum voltage (percentage)

The connected control loop output 0..100%is then scaled from minimum voltage to maximum voltage. 

For example in the EC fan control, if the fan is required to run always at minimum level, the minimum 
control output voltage can set to 10% (1V) and the maximum output 70% (7V). In this case the control 
loop output 0..100% is scaled to be 10..70% at the analogue output. This allows maximum noise 
levels to be limited and the fan to have a minimum fan speed. 

The values are available via the communication network from network master read/write. 

Relay Outputs / Fan Speed 
Control 
(SRC-701/SRC-703/SRC-704
H)

SRC-701(H), SRC-703 and SRC-704H have 3 relay outputs that be used to control 3-speed fans. The 
relay 1 is switched ON approx. 30% of fan demand, relay 2 is switched ON at approx. 60% of fan 
demand and relay 3 is switched ON approx 90% of fan demand. Only one relay is on at any given 
time. The relays are switched OFF approx 20% below the fan switch ON level.

NOTE:For the fan relay outputs to operate, the Y1 (Analogue Output Y1 Mode) has be set to 
’Modulating Fan’ (default setting).

NOTE:SRC-701H/704H relays are rated 7A resistive. SRC-701/703 relays are rated 0.5A 
resistive.

Relay Output / On-Off 
Control (SRC-703)

SRC-703 have 4th 230Vac relay that can be used to switch 230Vac On/Off. The output can be used to 
switch heating valves, cooling valves or plant enable outputs.This is done by configuring the output Y2 
setting to one of the dollowing settings:-

HEATING STAGE 1 STAT; thermostatic switching of output, 100% (SRT-703 RLY4 via Y2 ON) when 
Heating1 Stage at 10% or over, switches back to 0% (SRT-703 RLY4 via Y2 OFF) when Heating1 
Stage  output 0%

COOLING STAGE 1 STAT; thermostatic switching of output, 100% (SRT-703 RLY4 via Y2 ON)  when 
Cooling1 Stage at 10% or over, switches back to 0% (SRT-703 RLY4 via Y2 OFF)  when Cooling1 
Stage output 0%

FAN STAT; thermostatic switching of output, 100% (SRT-703 RLY4 via Y2 ON)  when Fan Loop at 
10% or over, switches back to 0% (SRT-703 RLY4 via Y2 OFF) when Fan Loop output 0%

As default for SRC-703 the Y2 has been configured as ’HEATING STAGE1 STAT’.

Summary of Contents for SRC-P-700 Series

Page 1: ...ic Summer Winter Time Change Over Product sheet CT2 161 Type SRC P 700 Product Selection Table 1 2 3 4 5 6 1 Device type Touchscreen Room Controller 2RI 1DI 3AO htg clg fan Schedule SRC P 700 Touchscr...

Page 2: ...maximum 63 devices MAC Addressing 0 127 via Touchscreen Device ID Default 651000 MAC Address Adjustable Communication 9k6 19k2 38k4 57k6 76k8 Baud Parity None Even Odd 1 or 2 Stop Bits adjustable thr...

Page 3: ...ommon RI1 Remote NTC10 Temperature Sensor Input 1 0 10V with AI option RI2 Remote NTC10 Temperature Sensor Input 2 0 10V with AI option Din Volt Free Digital Input Contact dry contact 485A Modbus BACn...

Page 4: ...nput 1 0 10V with AI option RI2 Remote NTC10 Temperature Sensor Input 2 0 10V with AI option Din Volt Free Digital Input Contact dry contact 485A Modbus BACnet MS TP RS485 A Connection 485B Modbus BAC...

Page 5: ...n Speed 1 On Off Valve RCOM Relay Common RLY2 230V 7A Relay Fan Speed 2 RLY3 230V 7A Relay Fan Speed 3 TR2 24Vac 1A Triac switched to 0V default Cooling PWM 24V 24Vac dc Supply G0 0V Common TR1 24Vac...

Page 6: ...Ring modulates based on how far from the Effective Heating Cooling Setpoint the temperature is When the difference is 2 C 3 6 F the Energy Ring is at full density calcSP HDz MEASURED TEMPERATURE CDz...

Page 7: ...in the stand by level switches the backlight OFF The screen backlight is automatically activated when it is touched Further Settings and Information The FURTHER SETTINGS screen shows additional user...

Page 8: ...re to fluctuate around the setpoint without heating or cooling valves starting to open The SRC has a built in lock that prevents cooling and heating demands to be on simultaneously The deadzone has an...

Page 9: ...target setpoint on the display is not changed during the limitation The limit icon indicates active limitation To see the effective limited setpoint enter Controller Status and Information display Not...

Page 10: ...C 6 0 0 6 0 1 6 0 2 0 1 0 V d c S R C 6 0 2 P W M Note If the 7 Day Schedule has been activated the device starts to use the operating mode set at the next switching point e g if the next switching p...

Page 11: ...chedule point regardless of the Boost Time or Current Measurement Please note that at the next switching time the target COMFORT ECO OFF BOOST must be different from the target in the current period i...

Page 12: ...O MATIC CONTROL 6 SPEED MANUAL FAN CONTROL M 17 33 0 50 67 83 100 A Auto SPEED SET BY CONTROLLER 100 0 50 100 0 33 67 0 100 M M M M M M M M M M M M A Auto SPEED SET BY CONTROLLER A Auto SPEED SET BY C...

Page 13: ...e actuators 100 CONTROL OUTPUT D e h u m i d i f i c a t i o n SP Setpoint e g 50 rH 100 Proportional Band e g 5 rH SP 0 Humidity rH 0 rH 100 rH LOOP OUTPUT H u m i d i f i c a t i o n 0 instead of 0...

Page 14: ...to open the operating mode does not change until the countdown timer has expired DIGITAL INPUT DELAY setting Note Resistive Inputs as a Digital Input operate with approx ten seconds delay and are not...

Page 15: ...apter 6 PORT REVERSE see 6 PORT VALVE control chapter reverse operation Analogue Output Scaling Output Limitation Each of the analogue outputs Y1 Y2 Y3 can have Output minimum voltage percentage Outpu...

Page 16: ...The SRC 700 controller can be configured to control Belimo 6 Port valve by selecting 6 Port or 6 Port Reverse mode for the analogue output Y1 Y2 Y3 The diagram below illustrates the operation Note Ana...

Page 17: ...ensor 2 Fault The typical alarm reasons are External sensor 1 Res1 fault when activated out of range External sensor 2 Res1 fault when activated out of range Built in sensor fault Digital Input Alarm...

Page 18: ...of the temperature control loop Set to 0 to disable 0 1 200 seconds Default 600s Heating Stages Number of Heating Stages 0 None 1 1 Stage Default 2 2 Stages Heating Stage 1 Dir Heating Stage 1 Directi...

Page 19: ...setting Disabled This is done by entering and exiting the System configuration menu Humidity Display Enable Disable Humidity Display if option fitted 0 Disabled 1 Enabled default Digital Input Mode Di...

Page 20: ...fault Anti JAM Valve Exercise 0 14 Days default 0 disabled PWM Period PWM Period SRC 702 SRC 704H 0 120 Seconds default 30 INPUTS OUTPUTS Parameter Name Description Range FAN BOOST TIMES Parameter Nam...

Page 21: ...ACnet Baud Rate 0 9600 Default 1 19200 2 38400 3 57600 4 76800 Parity Only Modbus BACnet versions Parity 0 None Default 1 Odd 2 Even Stop Bits Only Modbus BACnet versions Stop Bits 0 1 Stop Bit Defaul...

Page 22: ...gister Parameter Description Data Type Raw Data Range FUNCTION CODE 01 READ COILS FUNCTION CODE 05 WRITE SINGLE COIL FUNCTION CODE 15 WRITE MULTIPLE COILS 100 OFF Mode Override 0 1 Off On 101 ECO Mode...

Page 23: ...ge Default 2 2 Stages 111 Heating Stage 1 Direction Unsigned 16 0 1 0 Reverse Default 1 Direct 112 Heating Stage 2 Direction Unsigned 16 0 1 0 Reverse Default 1 Direct 113 Number of Cooling Stages Uns...

Page 24: ...put Y2 Override Value Unsigned 16 0 1000 0 100 0 10 0V Default 0 136 Analogue Output Y3 Override Value Unsigned 16 0 1000 0 100 0 10 0V Default 0 137 Y1 Minimum Output Unsigned 16 0 1000 0 100 0 Defau...

Page 25: ...Unsigned 16 0 4 0 Lock mode disabled default 1 On Off workable only 2 Temp settings only available 3 All buttons disabled 156 Lock Mode Password Unsigned 16 0 9999 0000 9999 157 Boost Time Unsigned 16...

Page 26: ...ride Level 1 100 On Off 50 3 Levels 33 4 Levels 3 Override Level 2 100 3 Levels 66 4 Levels 4 Override Level 3 100 4 Levels 178 Override Blinds Notes After overriding the level the parameter returns t...

Page 27: ...gned 16 0 2400 0 2400 Default 2200 215 Tuesday Switching Time 1 Target Unsigned 16 0 3 0 Comfort Default 1 ECO 2 Off 3 Boost 216 Tuesday Switching Time 2 Target Unsigned 16 0 3 217 Tuesday Switching T...

Page 28: ...0 2400 0 2400 Default 0600 261 Sunday Switching Time 2 Unsigned 16 0 2400 0 2400 Default 1000 262 Sunday Switching Time 3 Unsigned 16 0 2400 0 2400 Default 1300 263 Sunday Switching Time 4 Unsigned 16...

Page 29: ...ue Please note AV1 AV10 are Read Only 31 AV 0 Built In Sensor Read Only2 AV 1 RI_1 RI1 Temperature AI1 R O2 AV 2 RI_2 RI2 Temperature AI2 R O2 AV 3 Target Calculated Setpoint R O2 AV 4 Humidity Read O...

Page 30: ...ry Properties 40106 Setpoint Adjust Minimum REAL 20 0 0 0 C F Default 3 0 40107 Setpoint Adjust Maximum REAL 0 0 20 0 C F Default 3 0 40110 Number of Heating Stages Unsigned 0 None 1 1 Stage Default 2...

Page 31: ...ult Cooling Stage 1 Unsigned 40143 Anti JAM Time out Unsigned 0 14 Days 0 Disabled Default 40144 RI1 Mode Unsigned 0 Disabled default 1 Room NTC10 Control 2 Floor NTC10 High Low Lim 3 Aux Loop 4 Netwo...

Page 32: ...midity Unsigned 0 Disabled 1 Enabled default 40165 Show Swap Temperature Units Icon Unsigned 0 Disabled default 1 Enabled 40166 Zone 1 Room Sensor Text Unsigned 1 Room Default 2 Floor 3 Outside 4 Zone...

Page 33: ...seconds Default 0 0 Infinite Delay 40190 Aux Heating Loop Proportional Band Unsigned 1 0 50 0 C F Default 4 C 40191 Aux Heating Loop Control Integral Action Unsigned 0 1 200 seconds Default 600 40192...