98
A-96.250.581 / 220616
AMI Codes-II CC
Program List and Explanations
5.3.2.400
Hysteresis:
within the hysteresis range, the relay does not switch.
This prevents damage of relay contacts when the measured value
fluctuates around the alarm value.
5.3.2.50
Delay:
Duration, the activation of the alarm relay is retarded after
the measuring value has risen above/fallen below the programmed
alarm.
Range. 0–600 Sec
The relays may be used to drive control units such as solenoid
valves, membrane dosing pumps or motor valves. When driving a
motor valve both relays are needed, relay 1 to open and relay 2 to
close the valve.
5.3.2.22
Parameter:
Choose on of the following process values.
Free av. chlorine (
Free available chlorine
)
Total chlorine 1
Total chlorine 2
Calc. monochl. (
Calculated monochloramine
)
Calc. comb. cl. (
Calculated combined chlorine
)
Calc. dichloramine (
Calculated dichloramine
)
Temperature
Sample flow
pH
5.3.2.32
Settings
:
Choose the respective actuator:
Time proportional
Frequency
Motor valve
Parameter
Range
Free av. chlorine
0–10 ppm
Total chlorine 1
0–10 ppm
Total chlorine 2
0–10 ppm
Calc. monochl.
0–10 ppm
Calc. comb. cl.
0–10 ppm
Calc. dichloramine
0–10 ppm
Temperature
0 to +100 °C
Sample flow
0 –200 B/s
pH
0–14 pH
5.3.2.1
Function = Control upwards/downwards: