Page 8
Installation Information
International Dual Fuel (ICBDF) Series
International Dual Fuel (ICBDF) Series
2-3
#814889 - Revision A- July, 2010
Gas Requirements
Wolf ICB Dual Fuel Ranges are manufactured to work with natural gas or LP gas (Liquid Propane gas). The model /
serial rating plate, located on the bottom of the control panel assembly just above the oven door on the far right, has
information on the type of gas that should be used. If this information does not agree with the type of gas available,
check with the local gas supplier.
Natural Gas Manifold Pressure:
Standard natural gas orifices on the appliance are set for 20 m bar (8” WC - Water Column Pressure).
Liquid Propane Manifold Pressure:
The standard propane gas orifices on the appliance are set for 37 m bar (14.1” WC - Water Column Pressure).
Gas Supply Line Size:
•
3/4 inch rigid pipe to the range location
•
For LP gas, piping or tubing size can be 13mm (1/2") minimum.
NOTE
:
A smaller size pipe on long runs may result in insufficient gas supply.
A CSA design-certified, 914 mm long, 123mm (1/2") or 19 mm (3/4") ID, flexible metal appliance connector is recom-
mended for connecting this range to the gas supply line.
Do not kink or damage the connector when moving the range.
Gas Supply Pressure:
•
Maximum line pressure for natural = 25 m bar (10” WC) gas and LP = 45 m bar (18” WC); 3.5 kPa (1/2 psi).
•
Minimum line pressure for natural gas is 17 m bar (7 WC).
•
Minimum line pressure for LP gas is 25 m bar (10” WC).