© STULZ GmbH, Hamburg
DE / 06-2016 / 1000687
-
77
-
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A-
Maintenance
Assemble the unit in reverse order.
CAUTION
Trapped cables.
During installation, take care not to trap any
cables between parts of the housing!
Note
CAUTION
Flush water pipes.
Flush the water pipes with the highest possible
pressure before connecting units to the water
mains.
Note
9
Disinfect the water tank:
a) Brush or spray all parts with 5 %
hydrogen peroxide solution (H
2
O
2
) a
minimum of three times at 15-minute
intervals.
b) After an exposure time of approx.
30 min, rinse parts thoroughly several
times with water.
c) Flush water pipes with the highest
possible pressure before connecting
units to the water mains.
1
2
3
3
Item Description
1
Water tank
2
Oscillator
3
Mist outlet
4
Float switch
3
10
Summary of Contents for ENS 14 A