STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A-
Open-loop and closed loop control
Accessory set for controlling the STULZ UltraSonic humidifier
(ON/OFF)
Set
Transformer
TVS
diode
RC
element
Con tac-
tor
Condenser
Interference
suppression
filter
Proportional
adapter
Item
number
For mounting a two-point control
ENS 14 A
1 x 1300 VA
2 x
1 x
1 x
1 x
1 x
---
K87073
ENS 18 A
1 x 1300 VA
2 x
1 x
1 x
1 x
1 x
---
K87073
The optional accessory sets consist of unmounted components for installing in an on-site switch gear cabinet.
6.2.
Accessory sets (controlled by on-site switch gear cabinet)
Accessory sets consist of individual components for creating a control system in the on-site switch gear
cabinet. This control system can also be used with an external control signal. When wiring the switch
gear cabinet, connect the supplied TVS diodes parallel to the Nebulizer print plate to protect the trans
-
ducers. In addition, use the supplied contactor for the water tank fill level and connect it to the supplied
RC element.
CAUTION
The wrong contactor coils can cause damage.
Different contactor coils can damage the unit!
●
Use genuine STULZ spare parts.
IMPORTANT
CAUTION
Use the maximum hygrostat.
The use of a maximum hygrostat is urgently recommended for this type of humidifier. Over-humidifica
-
tion of the ventilation duct needs to be avoided for reasons of hygiene.
●
Use genuine STULZ accessories.
IMPORTANT