Product description
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A-
Permitted materials for demineralized water
Permitted material
Maximum temperature
Stainless steel (1.4571)
>100°C
PE (polyethylene)
60°C
PP (polypropylene)
>100°C
PVDF (polyvinylidene fluoride)
>100°C
PA (polyamide)
60°C
4.7.
Application limits
During the planning and installation of UltraSonic humidifiers, take care to ensure that all materials that
come into contact with demineralized water are resistant to it. See table at bottom of page for the most
important materials
.
Application limits
Water quality
< 80 μS/cm, up to 150 μS/cm for brief periods
Supply voltage to control unit
230 V ± 10%
Voltage to ultrasonic humidifier
48 V ± 10%
Water pressure
0.5 bar to 6 bar upstream of ultrasonic humidifier
Water temperature
+5°C to +40°C
Air humidity
≤ 90% RH
Air flow rate
1,5 - 3,0 m/s
* For individual operating hours, e.g. during start-up or during the delivery time of new filter cartridges.
No longer than 5% of operating hours in total. Also see "4.9. Water treatment" on page 20.
CAUTION
Reducing conductivity.
Depending on the planned application, it may make sense to further reduce conductivity.
This must be done by the plant operator.
Note
CAUTION
High dust content.
If the air has an unusually high dust content (e.g. silicon powder in printing presses), the
air must be filtered, because deposits of dust on the water reduce the capacity of the humidifier.
The air filter is not included with delivery, and needs to be provided by the plant operator.
Note
CAUTION
Quality of drinking water.
The conductivity of the treated water may vary depending on the quality of the available drinking water.
Note
CAUTION
Room temperature below 0°C.
The humidifier must not be used if the room temperature drops below 0°C.
●
Drain the water tank of the units.
IMPORTANT
CAUTION
Resistant materials.
The connection between the demineralization system and the humidifier must consist of a material that
is resistant to demineralized water.
•
PE or stainless steel (1.4571)
IMPORTANT