© STULZ GmbH, Hamburg
DE / 06-2016 / 1000687
-
85
-
STULZ UltraSonic -System for duct humidification ENS 14 A - 18 A-
Maintenance
Proceed as follows to replace the atomizer PCB:
9
Slacken the two screws and remove the
atomizer PCB.
8
Remove the orange and yellow cables of
the oscillator, and the black and white or
red and green supply cable.
CAUTION
Replacing the oscillator.
We recommend also replacing the oscillators if
you are replacing the atomizer PCB.
Note
3
4
10
Use the silicone base!
11
Replace the PCB with a genuine spare
part from STULZ.
CAUTION
Risk of injury from hot PCBs.
The atomizer PCB can be very hot immediately
after operation.
•
Always allow PCBs time to cool down.
Item Description
1
Oscillator
2
Atomizer PCB
3
Supply cable (black/white)
4
Supply cable (red/green)
5
Screw
6
Silicone base for atomizer PCB
2
4
3
3
6