STULZ CyberRow DX Series Installation, Operation & Maintenance Manual
4-14
4.4.5 Remote
On/Off
For Remote On/Off operation, terminal positions are
provided to connect a remotely located, On/Off switching
control device. If the A/C unit is turned on and the
E2
controller receives a remote input signal to turn off the
A/C unit, the controller disables all control outputs and a
message "Off by Remote Shutdown" appears in the main
display screen. The A/C system will automatically be re-
enabled when the remote On/Off signal calls for the A/C
unit to turn back on.
The control device may be an On/Off switch, thermostat
or a humidistat. If customer provided, the remote On/Off
control contacts must be sized appropriately. The Remote
On/Off contacts must have a minimal rating of 24 VAC.
Refer to the electrical drawing included with the A/C unit
for the electrical specifi cations and for wiring details.
4.5 Menu
Screens
4.5.1 Main
Menu
MAIN MENU
Factory
INFO
Alarm Log
The Main Menu is accessed from the Main screen by
pressing the
Prg
key. The Main Menu screen provides a
complete listing of the menu loops that are available. You
may scroll through the menu categories using the Up (
) and Down
( )
arrow keys. From the Main Menu screen
you may select from among the following standard
menus:
"Info"
- Displays basic read-only status information.
Allows you to monitor system operational parameters. No
password is needed at this level.
"Alarm Log"
- Displays all alarms and "power-ups"
in sequential order with a time and date stamp. No
password is needed at this level.
"Control"
- Allows modifi cation of basic control
parameters such as setpoints and clock. Level 1
password is needed to enter this menu.
"Service"
-
Allows modifi cation of advanced control
parameters such as offsets, blower speed, BMS set up and
permits the user to save customer parameters and reset the
controller to the customer or factory default values. Level 2
password is needed to enter this menu.
"Factory"
- Allows modifi cation of more advanced
control parameters such as sensor scaling, start-up
delays and grouping parameters. Level 3 password is
needed to enter this menu. Entry to the Factory menu
is intended for qualifi ed technicians working under the
guidance of STULZ Product Support during start-up
and commissioning of the A/C system. The password to
enter this menu may be obtained by contacting Product
Support (see section 6.0 of this manual).