STULZ CyberRow DX Series Installation, Operation & Maintenance Manual
4-3
4.1.3 Controller I/O Module
The controller is a microprocessor based I/O module
mounted inside the A/C system electric box (see Figure
11). The controller I/O module contains the software that
manages the operating parameters of the A/C system.
1
2
4
3
6
5
7
Figure 11- Controller I/O Module
4.1.3.1 Controller I/O Module Layout
The controller I/O module contains the logic and input/
output terminals. See Figure 11 for details of the
controller I/O module layout. The item numbers that
follow coincide with the call-outs in Figure 11.
1. Connection (J10) for interface display panel
2. Connection for pLAN (J11)
3. Hatch for BMS or network card
4. Power on LED (Yellow)
5. Signal LEDs (Red, Yellow, Green)
6. Hatch for expansion I/O module(s)
7. Power connector (J1)
4.1.4 BMS
Interface
The
E2
series controller may incorporate a BMS network
card equipped with a communication port (Figure 12).
This can be fi eld connected through a serial interface to
a Building Management System via Modbus, BACnet,
SNMP or HTTP protocol as confi gured by the factory. A
controller interfaced to a network must be confi gured for
BMS communication.
BACnet IP, BACnet Ethernet,
HTTP, SNMP, & Modbus IP
BACnet MS/TP
Modbus RTU
Figure 12- BMS Interface Ports
Summary of Contents for CyberRow DX CRS-042-G