STULZ CyberRow DX Series Installation, Operation & Maintenance Manual
4.5.5.9 Save
Confi guration
SERVICE
BMS Comm
SAVE CFG
Factory
The default setpoints may be restored and passwords may
be changed from the Service>Save Cfg menu.
Customer Save
Save Parameters
No
Restore Parameters
To Customer:
No
To Factory:
No
The fi rst Service>Save Cfg menu screen allows you
to save any adjustments made in Service level menu
screens as the new "Customer" parameters or, restore the
controller to the previously saved "Customer" parameters.
The user may also restore the controller to original factory
default parameter values shown in Table 1.
Use the
Enter (
)
key to move the fl ashing cursor to the
fi eld you wish to confi rm and press the
Up ( ) or Down
( )
arrow key. The word "
No
" will momentarily change to "
Yes
"
indicating the command has been accepted. Then press
the
Enter (
)
key sequentially until the fl ashing cursor
returns to the top left corner of the screen.
The table that follows are the Factory default parameters.
Table 1- Factory Default Setpoints
PARAMETER
DEFAULT VALUE
Temperature Setpoint
72° F
Compressor Cut- in
74° F
Compressor Cut- out
72.3° F
Minimum Fan Speed
40%
Maximum Fan Speed
100%
Dehumidifi cation Fan
Speed
60%
Humidity Setpoint
45% RH
Dehumidify Cut-in
50% RH
Dehumidify Cut-out
47% RH
4-30
Set Passwords
Control:
1
Service:
2
The second Service>Save Cfg menu screen allows you to
set new passwords for entering the Control and Service
menus.
4.5.5.10 Factory Menu
SERVICE
Save Cfg
FACTORY
Cool
The Factory menu loop may be accessed from the
Service>Factory screen. You must enter the factory level
password to gain access to the loop. Contact STULZ
Product Support for the password and for guidance when
adjustments must be made at this level.