STULZ CyberRow DX Series Installation, Operation & Maintenance Manual
4-47
4.9.3 Boolean Values for HTTP, SNMP / Modbus Coils / Binary Values for BACnet
BMS
Address
Modbus
Address
BACnet
Address
Description
Default
Direction
1
002
1
Global alarm output
0
R
2
003
2
System on status
0
R
3
004
3
Airfl ow has been proven
0
R
4
005
4
Call for cooling
0
R
5
006
5
Call for humidifi cation
0
R
6
007
6
Call for dehumidifi cation
0
R
100
101
100
BMS value to pause the unit
0
R/W
101
102
101
BMS value to reset alarms
0
R/W
102
103
102
Force rotation of units in group manual or BMS
0
R/W
103
104
103
BMS value to switch CW sources
0
R/W
104
105
104
BMS value to switch dual power primary
0
R/W
105
106
105
BMS value to activate lockout function
0
R/W
106
107
106
Reset dirty fi lter alarm
0
R/W
4.9.4 Alarm Packed Bit Variables
Bit
Alarms 1
Alarms 2
Alarms 3
0
Emergency shutdown
Middle fan alarm
Reserved
1
Remote shutdown
Upper fan alarm
Reserved
2
Customer Alarm 1
Lower fan alarm
Reserved
3
Airfl ow
High temperature
Reserved
4
Filter
Low temperature
Reserved
5
Fire/Smoke
High humidity
Reserved
6
Water detection
Low humidity
Reserved
7
Condensate pan
High water temp CW1
Reserved
8
Moisture
Low water temp CW1
Reserved
9
Circuit 1 low pressure
Customer Alarm 2
Reserved
10
Circuit 1 high pressure
Customer Alarm 3
Reserved
11
Pump
Flow alarm (temp sensors)
Reserved
12
Dual power input A
Flow alarm (fl ow switch)
Reserved
13
Dual power input B
Reserved
Reserved
14
Humidifi er
Reserved
Reserved
15
Loss of power
Reserved
Reserved