StecaGrid 3600/x
StecaGrid 4200/x
Rated frequency
50 Hz and 60 Hz
Grid type
L / N / PE (protective earth)
Grid frequency
45 Hz ... 65 Hz (depending on the country settings)
Power losses in nighttime
operation
< 2 W
Feeding phases
single-phase
Distortion factor (cos phi = 1)
< 2 %
Power factor cos phi
0.95 capacitive ... 0.95 inductive
Characterization of the operating behaviour
Maximum efficiency
98.6 %
European efficiency
98.3 %
98.2 %
CEC efficiency
98.3 %
98.2 %
MPP efficiency
> 99.7 % (static), > 99 % (dynamic)
Efficiency values (at 5 %, 10 %,
20 %, 25 %, 30 %, 50 %, 75 %,
100 % of the rated output
power) at rated voltage
95.8 %, 97.4 %, 98.2 %, 98.3
%, 98.4 %, 98.4 %, 98.1 %,
97.7 %
96.2 %, 97.6 %, 98.3 %, 98.3
%, 98.3 %, 98.2 %, 97.9 %,
97.4 %
Efficiency values (at 5 %, 10 %,
20 %, 25 %, 30 %, 50 %, 75 %,
100 % of the rated output
power) at minimum MPP voltage
96.3 %, 97.7 %, 98.5 %, 98.6
%, 98.6 %, 98.5 %, 98.3 %,
97.9 %
96.7 %, 98.0 %, 98.5 %, 98.6
%, 98.6 %, 98.4 %, 98.1 %,
97.6 %
Efficiency values (at 5 %, 10 %,
20 %, 25 %, 30 %, 50 %, 75 %,
100 % of the rated output
power) at maximum MPP voltage
95.2 %, 97.0 %, 97.8 %, 98.0
%, 98.1 %, 98.0 %, 97.8 %,
97.5 %
95.7 %, 97.0 %, 98.0 %, 98.1
%, 98.2 %, 97.9 %, 97.6 %,
97.2 %
Efficiency reduction in the case
of a rise in ambient temperature
(at temperatures > 40 °C)
0.005 %/°C
Efficiency change in the case of
deviation from the DC rated
voltage
0.002 %/V
Own consumption
< 4 W
Derating at full power
from 50 °C (T
amb
)
from 45 °C (T
amb
)
Switch-on power
10 W
Switch-off power
5 W
Safety
Protection class
II
EN
747,431 | Z09.2 | 18/02/2016
79
Summary of Contents for coolcept StecaGrid 1500
Page 1: ...Installation and operating instructions EN coolcept coolcept x 747 431 Z09 2 2016 02 18...
Page 57: ...Fig 20 Email confirming successful registration EN 747 431 Z09 2 18 02 2016 57...
Page 85: ...Appendix EN 747 431 Z09 2 18 02 2016 85...
Page 93: ...747 431 Z09 2 2016 02 18...
Page 94: ......