Table 3. Settings (continued)
Table 3 Settings continued next page.
Index
Min
Value
Max
Value
Description
Defaults
Single
Dual
3
5
99
Open Check Length Open Check Length is the percent of door
length in which the door starts to slow down to
open check speed.
This parameter typically is adjusted based on
door weight and open speed setting.
40
25
4
5
99
Close Check Length Close Check Length is the percent of door length
in which the door starts to slow down to Close
Check Speed.
This parameter typically is adjusted based on
door weight and Close Speed setting.
15
15
5
1
99
Reduced Open
Length
Reduced Open Length is the percent of door length
from the full open position the door will stop at if in
reduced open mode.
1
1
6
1
99
Hold Open Delay
Delay that the door stays open after all sensors
have cleared (0 to 25 seconds).
15
15
7
0
3
Lock Logic
Select to choose desired Lock Logic.
NOTE: Dura-Max 5400 logic is different and has
its own two options:
00 = Fail Safe (unlocked when power
is removed),
01 = Fail Secure (locked when power
is removed),
02 = Dura-Max Fail Safe (unlocked when power
is removed),
03 = Dura-Max Fail Secure (locked when power
is removed).
1
1
8
1
99* Open Torque
Open Torque is the torque used during normal
operation following the end of open startup
length.
This torque must be set to comply with BHMA/
ANSI door force requirements.
This parameter sets the maximum current
available to the motor which is directly
proportional to the door force. This torque
setting is used in conjunction with open speed.
40
45