ERROR 

CODE

MEANING

CAUSE & REMEDY

E1

,

 

E4

Drive Error

Cause:

The Circuit Board is poten ally damaged/faulty.

Remedy

:

Try ac va ng the door again. If the fault persists, return the Circuit board for 

repair/replacement. 

Fu

Fuse Blown

Cause

:

The 20A fuse on the Circuit Board has blown.

Remedy

:

The fuse may have blown due to excessive forces being applied during the door 

opera on. Ensure that the door is moving easily and is balanced and replace the 

fuse with a new 20A fuse. 

If the fault persists, return the Circuit Board for repair/replacement.

di

Motor Disconnect

Cause

:

The Circuit Board has detected a motor disconnec on.

Remedy

:

Check that the motor wires are correctly connected to the Circuit Board. If the fault 

persists, return the Circuit Board for repair/replacement.

nL

No Limits

Cause:

Limits not programmed.

Remedy:

Program the limits.

24

WARRANTY

DACE warrants that LUX DC12 operators will be free from defects in material and workmanship for a period of 24 

months of opera on. Where opera onal data is not available, the warranty claim must be accompanied by the 

original invoice. In the event that both opera onal data and the original invoice are not available the warranty will 

be deemed to have been in effect from the date of manufacture. This warranty only covers the gearbox and 

onboard controller, it excludes any other products that might have been supplied with the operator such as a 

transformer, ba ery or beams (warranty informa on regarding products may be found in the installa on guide 

pertaining to each product). This warranty explicitly only covers the repair, components and labour carried out at 

DACE, all other costs will be for the account of the purchaser.
This warranty does not apply if:

the operator was subjected to misuse,

the operator was installed contrary to the specifica ons provided in this manual,

any a empt has been made to repair the goods by any workshop and/or person not authorised to do so by

 DACE or

if goods have been repaired using components not tested, passed or authorised by DACE

This warranty does not cover:

any Acts of God, including lightning, hail, water, power surge, insect damage, corrosion,

the transport, or costs associated with the transport, of the defec ve product to a designated DACE repair 

centre,

contractor or other third party costs

any other costs that may have been incurred by the purchaser or any other party or 

on site repairs.

This warranty is a factory warranty, all goods will be repaired at the factory or one of the DACE designated repair 

centres.

In the case of interna onal customers, the defec ve product must be returned to the supplier from where the 

product was purchased WITH PROOF OF PURCHASE FROM THAT SUPPLIER.

HEAD OFFICE

: Kwazulu Natal, SOUTH AFRICA

+27 31 825 7484

[email protected]

www.dace.co.za

Facebook.com/DuraAccessControlEquipment

12 Volt DC

Vertical Mount Roll Up

Operates a Single or Double Garage

Door

Garage Door Operator 

IN

ST

AL

LA

TI

O

N

 &

 U

SE

 

M

AN

U

AL

 

Ver 1.01 

 

Summary of Contents for LUX DC12

Page 1: ...the operator such as a transformer ba ery or beams warranty informa on regarding products may be found in the installa on guide pertaining to each product This warranty explicitly only covers the repa...

Page 2: ...wo of the remote bu ons simultaneously This will reduce the risk of accidentally ac va ng the Lockout func on ES Encoder Stop Fault Obstruc on Cause The operator has stalled This could be as a result...

Page 3: ...ers The advanced engineering and high quality construc on of each DACE product we build is something of which we are proud The LUX DC12 garage operator is packed with features to bring you convenience...

Page 4: ...energy instead of a buildings mains supply for charging the operator s ba ery Transformer An external device connected to the buildings mains supply via a plug point that reduces the mains voltage to...

Page 5: ...Board DuraOp cs Wireless Safety Beams REV LIMITS AUX LOCK 12V TRIG INF GND NO GND COM 12V 24V NC FET Power Input Cau on When ng a Magne c Lock to the door no NOT use the power from the operator as th...

Page 6: ...AYOUT CONTROL BOARD LAYOUT REV LIMITS AUX LOCK 12V TRIG INF GND Inputs Outputs Power Input 12 18V AC or 17 22V DC Solar ve ve Ba ery Cables Motor Wire Red Motor Wire Black Blue 20A Fuse Motor DBUS Inp...

Page 7: ...you to the Programming Menu Pr R c SET p r SET b c SET L E 18 L o SET 1 Ensure the ba ery is connected to the Operator 2 Press the SET bu on to enter the Programming Menu Pr 3 Press the DOWN bu on un...

Page 8: ...5 Press the DOWN bu on un l Lt Light is visible 6 Press and hold the remote bu on that is to be used to turn the operator light on and o Do not use the same bu on that was programmed to trigger the op...

Page 9: ...enu Pr 3 Press the DOWN bu on un l the Remote Menu rc is visible 4 Press the SET bu on to enter the Remote Menu The display will change to LE Learn 5 To program a remote press and hold the remote bu o...

Page 10: ...hts or bypass alarm passives when entering the garage Press the SET bu on to enter the AL menu Press the UP or DOWN bu ons to scroll through the me op ons T0 to T9 Press the SET bu on to select the de...

Page 11: ...re is free movement of the Li ing Assembly on the Drive Channel Li the door s manually to various heights and ensure that the door s do not close under their own weight If they do then it will be nece...

Page 12: ...ng the door will stop brie y and then reopen to the fully open posi on If the door is opening and it is stopped within 30cm of the fully closed posi on it will con nue opening when it receives the nex...

Reviews: