Connecting Main Power Wiring
Warning
:
To prevent injury to personnel, incoming electrical power to the header must be de-energized
before connecting electrical service to the control box.
Warning
:
All electrical wiring must conform to National Electrical Code Requirements.
1.
DE-ENERGIZE
incoming electrical power to header.
2. Refer to Attachment 2, and, using wire nuts,
CONNECT
incoming line, neutral, and ground wires
to the controller power harness.
3. IF adhesive wire clamps will be used,
DE-GREASE
metal surfaces on inside of header cover
where clamps will mount.
4.
SECURE
wiring to top of the header track tube, and
ENSURE
the following:
• All wires are clear of belts and belt brackets.
• Header cover opens and closes without interference.
Connecting Accessories (As Applicable)
Re
fer to Attachments 2 and 3, and CONNECT any of the following subsystems to the iQ Controller:
• Function switch (rotary, rocker and “POWER” switch wiring).
• Stanguard
TM
threshold sensor.
• Doorway holding beam(s).
• Breakout switch.
• Solenoid lock.
• SU-100 motion sensor(s) wiring (refer to Stanley Document #203957).
• Optex X Zone T and X Zone ST Sensor(s) wiring.
• Push plate wiring.
• Door position switch closed contact (with door closed).
• Hotron HR100 ST Sensor(s) wiring.
TUNE-IN INSTRUCTIONS
Warning
: The door path must be free of objects and remain clear until the First Install Sequence (FIS)
is complete. During this sequence the sensors are inactive and the door has no SAFETY. To stop the door,
turn power off
or put the
doors into breakout
.
NOTES:
1.
Tune-In
: The iQ Controller can be tuned-in using a handheld device or using the pushbutton switches
located on the controller. Tune-in using a handheld device is the preferred method.
2.
Status Codes
: During normal operation, the digital display indicates status codes. The “UP” and “DOWN”
pushbutton switches can be used to enter and display data values. The user interface values are shown
in Tables 2 through 4.