F
Serial Control Level
(The Factory Default Setting for Serial Control Level is “NONE”).
To make a change to the Serial Control Level feature, follow the step by step procedure outlined below.
Note: The five-position switch and red selection button are located on the dispenser control board. This
should only be set to CONTROL on the primary dispenser. All other dispensers should be set to NONE.
IMPORTANT: Please note the original switch settings before starting this procedure. You will need to
return the switches to this original setting to assure proper operation after making any changes. As a
convenience, you can enter these original settings in the diagram to the right by simply marking an “X”
for UP (ON) or DOWN (OFF) on each switch.
1.
Activate the Serial Control Level Feature programming mode by setting:
Switch 1–ON; Switch 2-OFF; Switch 3-OFF; Switch 4-ON; Switch 5-ON
2.
Press the red selection button one time.
3.
Advance to the Serial Control Level setting step by setting;
Switch 1-ON; Switch 2-OFF; Switch 3-OFF; Switch 4 –OFF; Switch 5-OFF
4.
Press the red selection button two times.
5.
Now set switches to desired setting Choice numbers 1 through 3 as per the cart below. Once you’ve
made your selection, press the red selection button one time.
Example: Set switches to match Choice 2 if you want the Serial Control Level set to CONTROL
(Switch 1-ON; Switch 2-OFF; Switch 3-OFF; Switch 4 –ON; Switch 5-OFF)
6.
End the programming sequence by resetting the switch to their original settings, and then press the
red selection button one time to put the machine back into service.
SERIAL CONTROL LEVEL CHOICES
CHOICE
SETTING
(level)
SWITCH POSITIONS
SW2
SW3
SW4
SW5
1
NONE
DOWN
DOWN
DOWN
UP
2
CONTROL
DOWN
DOWN
UP
DOWN
3
CONTROL RELAXED
DOWN
DOWN
UP
UP
12 345