Ex n HART universal module, Zone 2
Series 9469/35
6.2
Terminal Assignment of the pluggable Terminal X1
For the module, a pluggable terminal X1 (245090 spring clamp terminal) for connecting
field devices is available as an accessory (not included in the scope of delivery of the
module). The X1 plug-in terminal has 24 clamping units for connecting the field cables.
19079E00
All earth connections (channel 0 to 7) are connected to each other.
The output current must flow back via its earth connection.
6.3
Connection Diagram for Field Devices
Terminal X1
Function
Channel 0
1
2
3
4
5
6
7
Output (+24 V)
–
–
–
–
9
13
17
21
(I
out
) / signal (U
in
)
1
3
5
7
10
14
18
22
(I
in
)
–
–
–
–
11
15
19
23
Earth (-)
2
4
6
8
12
16
20
24
2-conductor,
analogue
In / out
0/4 to 20 mA
3- / 4-
conductor,
analogue
In
0/4 to 20 mA
Digital in
24 V contact
With/without
LFD
(line fault
detection)
3-conductor
PNP proximity
switch
With/without
LFD
(line fault
detection)
Digital out
24 V / 0.5 A
20040E00
Parallel switching of outputs in order to increase the current is not
permissible.
Only connect a 3-conductor PNP proximity switch. An NPN connection is
not allowed.