Communication: Port Settings
Port Address
[1]
This parameter establishes the MODBUS RTU address. MODBUS RTU requests will only be processed
if the configured port address of the meter matches the request address found in the MODBUS RTU
packet. The range of addresses supported by MODBUS RTU is 1…247. MODBUS RTU request packets
with an address of 0 imply the packet is to be treated as a broadcast packet.
To change the port address, follow these steps from the
Port A Settings
menu:
1. Select
Port Address
to view the
Port Address
display.
2. Select the desired port address
(1…247)
.
3. Press
[E]
to save the option and to return to the
Port A Settings
menu.
External Port
Address
[1]
For PROFIBUS® use only. This parameter allows configuration of the PROFIBUS DP daughterboard
address.
Baud Rate
[9600]
The following Baud Rates are supported
• 9600
• 19200
• 38400
To change the baud rate, follow these steps from the
Port A Settings
menu:
1. Select
Baud Rate
to view the
Baud Rate
display.
2. Select one of the following baud rates:
9600
,
19200
or
38400
.
3. Press
[E]
to save the option and to return to the
Port A Settings
menu.
Data Bits
[8 bits]
The Data Bits parameter configures the port data bits. The following data bits are supported:
• 8
bits
• 7
bits
• 5
bits
To change the data bits, follow these steps from the
Port A Settings
menu:
1. Select
Data Bits
to view the
Data Bits
display.
2. Select one of the following:
8 Bits
,
7 Bits
or
5 Bits
.
3. Press
[E]
to save the option and to return to the
Port A Settings
menu.
SSK
513
Electromagnetic Flow Meter
Page 40
March 2014