Input/Output
Description
Terminal
Analog Output
0…20 mA Resistive Load < 800 ohms
4…20 mA Resistive Load < 800 ohms
0…10 mA Resistive Load < 800 ohms
2…20 mA Resistive Load < 800 ohms
16 (+)
15 (–)
Digital Output 1
Passive max. 30V DC, 100 mA
Active 24V DC, 50 mA (set Jumper JP1)
Max. Frequency 10 kHz
1 (+) and 2 (–)
Digital Output 2
Passive max. 30V DC, 100 mA
Active 24V DC, 50 mA (set Jumper JP2)
Max. Frequency 10 kHz
3 (+) and 4 (–)
Digital Output 3
Passive Max 30V DC, 100 mA, 10 kHz
Solid State Relay 48V AC, 500 mA, 1 kHz
* Software configurable
10 (+) and 9 (–)
10 (+) and 11 (–)
Digital Output 4
Passive Max 30V DC, 100 mA, 10 kHz
Solid State Relay 48V AC, 500 mA, 1 kHz
* Software configurable
13 (+) and 12 (–)
13 (+) and 14 (–)
Digital Input
5…30V DC
8 (+) and 9 (–)
Communications
(Port A)
RS232, configurable, MODBUS RTU, or Remote
Menu.
7 GND
6 Rx
5 Tx
Analog Output Wiring Diagram
Figure 19: Analog Output Wiring Diagram
Installation & Operation Manual
Page 19
March 2014