IR3 Flame Detector User Guide
26
Performance Considerations
1.5.5 Output Signals
Outputs are available according to the default configuration or the wiring
options selected for the 40/40I detector. Determine the outputs for your
model according to Table 7.
The detector incorporates several types of output suitable to different
control systems:
0
–
20mA (stepped) with HART
Relays (alarm, fault, auxiliary)
RS-485 Modbus
Table 7: Available Output Types
Output Type
Version
Detector Status
Alarm Relay
40/40I
–
Options 1XXXX,
4XXXX, and 5XXXX
The relay is N.O.
40/40I
–
Options 2XXXX
and 3XXXX
The relay is N.O. and N.C.
Auxiliary Relay 40/40I
–
Options 4XXXX
and 5XXXX
The relay is N.O.
Fault Relay
40/40I
–
Options 1XXXX,
2XXXX, and 4XXXX
The relay is N.C. energized
40/40I
–
Options 3XXXX
and 5XXXX
The relay is N.O. energized
0
–
20mA
Current Output
40/40I
–
Option 1XXXX
Sink with the HART protocol,
(can be changed to Source
–
see Figure 10, Figure 11, and
40/40I
–
Options 2XXXX
and 3XXXX
Source with the HART
protocol
RS-485
All versions
Modbus protocol
Summary of Contents for SharpEye 40/40I
Page 2: ...www acornfiresecurity com www acornfiresecurity com ...
Page 12: ...www acornfiresecurity com www acornfiresecurity com ...
Page 32: ...www acornfiresecurity com www acornfiresecurity com ...
Page 46: ...www acornfiresecurity com www acornfiresecurity com ...
Page 54: ...www acornfiresecurity com www acornfiresecurity com ...
Page 55: ...Appendix 55 Appendix www acornfiresecurity com www acornfiresecurity com ...
Page 56: ...www acornfiresecurity com www acornfiresecurity com ...
Page 64: ...www acornfiresecurity com www acornfiresecurity com ...
Page 72: ...www acornfiresecurity com www acornfiresecurity com ...