Testing Procedures
Important:
If the detector is exposed to a flame simulator, the alarm and
accessory relays and 0
–
20mA are activated during the simulation.
Therefore, automatic extinguishing systems and any external devices which
may be activated during this process must be disconnected.
➣
To perform Flame Simulator Test:
1
Power up the system and wait up to 60 seconds for the detector to turn
to a normal state. The Power LED turns on.
2
Aim the SPECTREX Flame Simulator Model FS-1100 at the target point of
the detector (Figure 14), such that the radiation emitted by it is facing
directly towards the detector. (See
on page
3
Press the operation button once. After few seconds, a successful test
shows the results listed in Table 19.
Table 19: Results of Successful Flame Simulator Test
Component
Action
Notes
0
–
20mA
Turn to 20mA
For a few seconds and then returns to
4mA
Alarm Relay
Activated
For a few seconds and then returns to
Normal
Auxiliary Relay
Activated
For a few seconds and then returns to
Normal
Fault Relay
Remains active
during the test
LED
Red, steady
The detector is now ready for operation.
Summary of Contents for SharpEye 40/40I
Page 2: ...www acornfiresecurity com www acornfiresecurity com ...
Page 12: ...www acornfiresecurity com www acornfiresecurity com ...
Page 32: ...www acornfiresecurity com www acornfiresecurity com ...
Page 46: ...www acornfiresecurity com www acornfiresecurity com ...
Page 54: ...www acornfiresecurity com www acornfiresecurity com ...
Page 55: ...Appendix 55 Appendix www acornfiresecurity com www acornfiresecurity com ...
Page 56: ...www acornfiresecurity com www acornfiresecurity com ...
Page 64: ...www acornfiresecurity com www acornfiresecurity com ...
Page 72: ...www acornfiresecurity com www acornfiresecurity com ...