SharpEye
TM
IR3 Flame Detector User Guide
52
Maintenance
4.1.2 Periodic Procedures
In addition to preventive cleaning and maintenance, the detector should be
functionally tested every 6 months or as dictated by local codes and
regulations. These tests should also be conducted if the detector has been
opened for any reason.
4.1.2.1 Power-Up Procedure
Perform the power-up procedure every time power is restored to the
system. Follow the instructions described in
on page 47.
4.1.2.2 Functional Test Procedure
Perform a functional test of the detector as described in
on page 28.
4.1.3 Keeping Maintenance Records
Maintenance operations performed on a detector should be recorded in a log
book. The record should include the following:
Installation date
Contractor
Serial and tag number
Entries for every maintenance operation performed, including a
description of the operation, date, and personnel ID
If a unit is sent to SPECTREX or a distributor for service, a copy of the
maintenance records should accompany it.
Summary of Contents for SharpEye 40/40I
Page 2: ...www acornfiresecurity com www acornfiresecurity com ...
Page 12: ...www acornfiresecurity com www acornfiresecurity com ...
Page 32: ...www acornfiresecurity com www acornfiresecurity com ...
Page 46: ...www acornfiresecurity com www acornfiresecurity com ...
Page 54: ...www acornfiresecurity com www acornfiresecurity com ...
Page 55: ...Appendix 55 Appendix www acornfiresecurity com www acornfiresecurity com ...
Page 56: ...www acornfiresecurity com www acornfiresecurity com ...
Page 64: ...www acornfiresecurity com www acornfiresecurity com ...
Page 72: ...www acornfiresecurity com www acornfiresecurity com ...