TM 40/40I, Rev (14) February 2017
Flame Simulator FS-1100
75
D.1.4 Range
Table 28: Sensitivity Ranges
Sensitivity
Detection
Sensitivity Setting
(ft/m)
Maximum Testing
Distance (ft/m)
1 (Low)
50/15
6.6/2
2
100/30
19.6/6
3
150/45
29.5/9
4 (High)
215/65
39.3/12
Notes
:
The minimum distance from the detector is 30
”/
75cm.
At extreme temperatures, there is a 15% maximum reduction in the
range.
Important
: Keep the flame simulator in a safe place when not in use.
D.1.5 Charging the Battery
The flame simulator uses lithium-ion batteries as a rechargeable power
source. When the batteries are fully charged, the simulator operates at least
1,000 times without having to be recharged. The simulator will not operate
when the voltage from the batteries is lower than the required operational
level.
1
Simulator
2
Battery Pack
3
Locking Disc
4
Back Cover
Figure 16: Flame Simulator Battery Replacement
Summary of Contents for SharpEye 40/40I