SharpEye
TM
IR3 Flame Detector User Guide
36
Certification Instructions
Units may be painted or fitted with optional accessories, some of which
are made of a non-metallic material or have a non-metallic coating which
could potentially generate an ignition-capable level of electrostatic
charge under certain extreme conditions. Therefore, these units should
not be installed in a location where they may be subjected to external
conditions (such as high-pressure steam) which might cause a build-up
of electrostatic charges on the non-conducting surfaces. Cleaning of the
equipment (except window) should be done only with a damp cloth.
The 3 fastening screws used to screw on the cover of the flameproof
compartment have a yield stress of 344N/mm
²
. Any replacement
fasteners must have a yield stress of at least this value.
When the duct mount is fitted and the equipment is intended to be
mounted to a heated/cooled air duct/process vessel, it should be verified
that the temperature of the air duct/process vessel should not be
capable of heating or cooling any part of the equipment enclosure to a
temperature outside the marked maximum ambient temperature range
prior to switching the equipment on, when taking into account
surrounding ambient temperature.
2.4.2 General Instructions
The cable entry point may exceed 167°F/75°C. Suitable precautions
should be taken when selecting the cable.
The equipment may be used with flammable gases and vapors with
apparatus groups IIA, IIB, and IIC:
T4 in the ambient temperature range:
–
67°F/
–
55°C to
+167°F/+75°C.
T4 in the ambient temperature range:
–
67°F/
–
55°C to
+185°F/+85°C.
Installation should be carried out by suitably trained personnel in
accordance with the applicable code of practice such as EN 60079-
14:1997.
Inspection and maintenance of this equipment should be carried out by
suitably trained personnel in accordance with the applicable code of
practice such as EN 60079-17.
Repair of this equipment should be carried out by suitably trained
personnel in accordance with the applicable code of practice such as EN
60079-19.
The certification of this equipment relies upon the following materials
used in its construction:
Enclosure
: 316L Stainless Steel or Aluminum
Window
: Sapphire Glass
Summary of Contents for SharpEye 40/40I
Page 2: ...www acornfiresecurity com www acornfiresecurity com ...
Page 12: ...www acornfiresecurity com www acornfiresecurity com ...
Page 32: ...www acornfiresecurity com www acornfiresecurity com ...
Page 46: ...www acornfiresecurity com www acornfiresecurity com ...
Page 54: ...www acornfiresecurity com www acornfiresecurity com ...
Page 55: ...Appendix 55 Appendix www acornfiresecurity com www acornfiresecurity com ...
Page 56: ...www acornfiresecurity com www acornfiresecurity com ...
Page 64: ...www acornfiresecurity com www acornfiresecurity com ...
Page 72: ...www acornfiresecurity com www acornfiresecurity com ...