Table 5: Welding Immunity Distance
Sensitivity Setting
Detection Range
(ft/m)
Immunity Distance
(ft/m)
1
50/15
>6/2
2
100/30
>12/4
3
150/45
>17/6
4
215/65
>25/7.5
1.5.4
Visual Indicators
One 3-color LED indicator is located inside the detector window, as shown in
Figure 3. The detector statuses are listed in Table 6.
Table 6: LED Indications
Detector Status
LED color
LED mode
Fault, BIT Fault
Yellow
4Hz - flashing
Normal
Green
1Hz - flashing
Warning
Red
2Hz - flashing
Alarm
Red
Steady
Figure 3: Indicator LED