SharpEye
TM
IR3 Flame Detector User Guide
84
40/40I Flame Detector
E.1.2.1
Conditions for Safe Operating
The flame detector must consist only of the approved hardware and
software modules.
The 24V power supply must fulfill the requirements for PELV/SELV of EN
60950.
The automatic BIT (Built-In-Test) must be activated.
The setup parameters must be verified (as described in
Using the 0
–
20mA Interface for Alerting
on page 84, point
; and in
Using the Alarm Relay Contact for Alerting
on page 84, point
). The
function of the 40/40 Flame Detector (flame detection, function of the
0
–
20mA interface, and relay functions) must be checked completely.
E.1.2.2
Using the 0
–
20mA Interface for Alerting
The following parameters should be set:
Automatic BIT test = on
Connected to 0
–
20mA Terminals
The following allowed output current must be supervised with an
accuracy of ± 5%:
Normal State = 4mA
Warning State = 16mA
Alarm State = 20mA
The receiving device must be programmed to indicate a fault condition
when current levels reach overcurrent or undercurrent.
The 0
–
20mA can be used as low and high demand mode.
E.1.2.3
Using the Alarm Relay Contact for Alerting
The following parameters should be set:
Automatic BIT Test = on
Connected to N.C. contact of alarm relay terminals
Connected to fault relay terminals
T
he relay contacts (“alarm” and “faulty relay”) must be protected with a
fuse rated at 0.6 of the nominal specified relay contact current.
The maximum contact rating that is allowed per SIL-2 is 30VDC.
The contact of the alarm relay opens if there is a fire alarm.
During the forwarding and evaluation of the alarm, the relay contact
opens.
The alarm relay can be used as low demand only.
Summary of Contents for SharpEye 40/40I
Page 2: ...www acornfiresecurity com www acornfiresecurity com ...
Page 12: ...www acornfiresecurity com www acornfiresecurity com ...
Page 32: ...www acornfiresecurity com www acornfiresecurity com ...
Page 46: ...www acornfiresecurity com www acornfiresecurity com ...
Page 54: ...www acornfiresecurity com www acornfiresecurity com ...
Page 55: ...Appendix 55 Appendix www acornfiresecurity com www acornfiresecurity com ...
Page 56: ...www acornfiresecurity com www acornfiresecurity com ...
Page 64: ...www acornfiresecurity com www acornfiresecurity com ...
Page 72: ...www acornfiresecurity com www acornfiresecurity com ...