SharpEye
TM
IR3 Flame Detector User Guide
22
Performance Considerations
Alarm response times for a standard fire at a specified range are shown
Table 2.
Table 2: Sensitivity Range Levels
Level
Response Time (sec)
Sensitivity Range: ft/m
(for 1ft
2
/0.1m
2
n-heptane pan
fire)
1
3
50/15
2 (default)
5
100/30
3
8
150/45
4
10
215/65
For some typical ambient conditions, the Zeta parameter as defined in NFPA
72 for the detector is 0.005 (1/meter).
Note
: Zeta parameters may vary significantly with changes in temperature,
air pressure, humidity, visibility conditions, etc.
1.5.1.3 Other Fuels
The detector reacts to other types of fire as follows:
The baseline fire refers to n-heptane 1ft
2
/0.1m
2
and is defined as 100%
sensitivity.
For fuel fire
–
standard pan fire size: 1ft
2
/0.1m
2
.
For gas flame
–
30
”/
0.75m high, 10
”/
0.25m width plume fire.
Maximum Response Time: 10 sec.
Table 3: Fuel Sensitivity Ranges
Type of Fuel
Percent of Max. Distance
at Each Sensitivity Range
Max. Distance
(ft/m)
Gasoline
100%
215/65
N-Heptane
100%
215/65
JP5
70%
150/45
Kerosene
70%
150/45
Diesel Fuel
70%
150/45
Methane*
70%
150/45
LPG*
70%
150/45
Ethanol 95%
60%
135/40
IPA
60%
135/40
Methanol
55%
115/35
Polypropylene
55%
115/35
Paper
38%
83/25
*30
”/
0.75m high, 10
”/
0.25m width plume fire
Summary of Contents for SharpEye 40/40I
Page 2: ...www acornfiresecurity com www acornfiresecurity com ...
Page 12: ...www acornfiresecurity com www acornfiresecurity com ...
Page 32: ...www acornfiresecurity com www acornfiresecurity com ...
Page 46: ...www acornfiresecurity com www acornfiresecurity com ...
Page 54: ...www acornfiresecurity com www acornfiresecurity com ...
Page 55: ...Appendix 55 Appendix www acornfiresecurity com www acornfiresecurity com ...
Page 56: ...www acornfiresecurity com www acornfiresecurity com ...
Page 64: ...www acornfiresecurity com www acornfiresecurity com ...
Page 72: ...www acornfiresecurity com www acornfiresecurity com ...