GENERAL

Before installing the detector, the user must read 
these instructions carefully and store this manual 
for  future    reference.  BSR-6060/A/MAR  is  used 
on ships and is  a thermal and rate of rise detector 
simultaneously. It co-operates with 
BSR-2104/MAR, BSR-2114/MAR panels.
The  device  transmits  an  analogue  value  to  the 
panel  which  depends  of  the  area’s  temperature 
and  the  rate  of  temperature  rise.  The  analogue 

o

value  is  100  (temperature  56 C)  and  increases 
one unit per degree of  the temperature  increase. 

o

If  the  temperature  rises  rapidly  (over  5 C  per 
minute)  then  the  analogue  value  that  sends  the 
detector to the panel is 128. The factory setting of 
the panel is to issue an alarm when the analogue 
value is greater than 104. The panel   issues an 
alarm  if  the  temperature  rises  rapidly  or  if  the 

o

temperature  exceeds  the  60 C.The  user  can 

o

change this analogue value from 100(56 C) up to 

o

120(76 C).  The  detector  have  two  parts,  one 
plastic base which is installed on the ceiling and 
the main unit of the detector which is fastened to 
the  base  by  a  simple  turning  to  the  right.  The 
detectors  have  an  indication  led  which  lights 
continuously in case of fire detection until there is 
a reset signal from the panel.   When we silence 
the  sirens  the  LED  remains  lit  to  show  us  the 
detector that issued the alarm. The LED goes off 
when we RESET the panel. The indication led also 
flashes every 8 sec to indicate good operation.

ADDRESS SETTING

To set each detector’s address you have to use 
the  device  BSR-2143  photo.1.  (refer  to  it’s 
instruction  manual).  After  the  address  setting   
mark this number to the sticker on the detector’s 

base (ADR:XXX). Each detector must have an 
address with which it is recognized from the panel.
It`s forbidden for two devices with same addresses 
to be connect  to  the  same  loop. 
 

OPERATION CHECK 

It is advised to conduct a good operation test every 
6 months and every time the detector   position is 
changed. It is essential to have good air circulation 
inside  the detector. Therefore care must be taken 
so  that the vents of the detector are not covered. 

NOTE

The  detectors  must  be  placed  in  the  ceiling  on 
visible areas with no side obstacles and away from 
sides with no air circulation or strong air currents 

2     

and  vapors.  Each  detector  covers  almost  50  m
and the distance between two detectors must not 
exceed 15m. 
The  cables  cross  section  must  be  from  0.5  to 

2

1.5mm . 

ATTENTION!!

After the device is   installed, care must be   taken, 
so  that  the  detector  vents  are  not  blocked  by   
anything  (i.e.  dust,  paint).  Failing  to  do    so  will 
prevent the smoke particles to enter  the  detection  
chamber.

A f t e r  t h e  i n s t a l l a t i o n ,  i t  i s  t h e  s o l e 
responsibility  of  the  user  to  maintain  the 
detector  for  good  operation.

921606004_09_002

                         ADDRESSABLE RATE OF RISE HEAT DETECTOR

 BSR-6060/A/MAR

Page 1 of 3

Thank you for your trust in our products  

Olympia Electronics -  European manufacturer

103 (diam.) x 48 (height) mm

Alarm LED 

A2R

5 °C / min

IP22

EN 54-5, IEC 60092-504, IEC 60533

o

-10 to 60  C

Up to 95% 

2 years

145gr.

TECHNICAL CHARACTERISTICS

IDLE STATE POWER CONSUMPTION
ALARM POWER CONSUMPTION
SENSITIVITY

PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE

DEGREES OF COVER PROTECTION

OPERATION VOLTAGE

RELATIVE HUMIDITY

TYPICAL WEIGHT 

EXTERNAL DIMENSIONS 

GUARANTEE

INDICATORS
CLASS

18-30V DC

1.5 mA (with indication LED activated)

1mA