6
Electrical connection
►
Connect the DC lines as shown in section 15.2 (pg. 105).
Observe the following:
•
Starting from F1 connect the plus lead to the plus pole of battery module 0.
•
Proceeding from terminal block X3 connect the minus lead to the minus pole of
the last battery module (with the highest number). With
sonnenBatterie eco 7/2 this is battery module 0, with
sonnenBatterie eco 7/4: battery module 1, with
sonnenbatterie eco 7/6: battery module 2, with
sonnenbatterie eco 7/8: battery module 3, etc up to
sonnenbatterie eco 7/16: battery module 7.
•
In the case of storage systems without an add-on cabinet:
►
Wind up the two long DC lines and
fix them with cable ties.
Page 60 of 115
KD-262 | Part-No 52199 | EN | Version 1.00