Electrical connection
6
Figure 32: Connection without and with solar data logger
1
PV inverter
2
Solar data logger
You can connect the storage system (X1) to the PV inverter (1) direct (support by
the inverter) or by a solar data logger (2).
The electrician must select which state of the output terminals corresponds to
which output power of the inverter, or it depends on the supported values of the
inverter. Examples of advisable output power are as follows:
Step
Output power
0
100 %
1
60 %
2
30 %
3
0 %
KD-262 | Part-No 52199 | EN | Version 1.00
Page 53 of 115
1
1
2