6
Electrical connection
6.6.2 Connecting self-consumption switch
Terminal 30 is a switching output that is activated upwards of a certain generated
surplus.
Figure 27: Self-consumption switch
When the output is activated (24 V on terminal 30) the contactor K1ex switches
and the connected load is powered. The coil connection A2 of contactor K1ex can
be joined to terminal 8, 9, 10 or 11 of terminal block X1.
The maximum current over terminal 30 is 500 mA.
Page 48 of 115
KD-262 | Part-No 52199 | EN | Version 1.00
L
N
+24V
26
34
27 28 29 30 31 32 33
K1
ex
A1
A2