6
Electrical connection
6.5 Connecting Modbus cable
There is risk of damaging components if you install in the wrong sequence!
►
First connect the Modbus leads to the power meters and afterwards to
terminal block X1 in the storage system.
Communication between the power meters and the storage system is implemented
over Modbus. The Modbus cable transmits a data signal (A and B) and provides a
signal ground (GND).
Figure 26: Illustration of Modbus connection
1
Power meter
2
Modbus cable
3
Shield
4
Modbus connector on terminal block X1 in main cabinet
►
You must use the following cable:
Specification of the Modbus cable
Manufacturer
Lapp Kabel
Name
UNITRONIC® BUS LD 2x2x0,22
Number
2170204
Tools needed
O Stripping tool
O Wire stripping pliers
O Screwdriver 0,4 x 2,5
O Wire end ferrule crimping pliers
Page 42 of 115
KD-262 | Part-No 52199 | EN | Version 1.00
CAUTION
DANGER
WARNING
Notice
4
1
3
2
2
3
4
A1 A2
N L1 L2 L3
1