19
Rev. 2
IOM AI1/2/3/4 Del [s]
Delay for IOM ANALOG INPUT 1 to 4 alarm.
Step: 1 s
Range: 0 - 900 s
Hint:
IG-IOM/IGS-PTM analog inputs protection alarms can be configured the following way:
Configuration
Protection
Under
Protection is activated only when measured value is under measured
level.
Over
Protection is activated only when measured value is over measured
level.
Under+fls
Level 2 protection is activated by Sensor Fail as well.
Over+fls
Level 2 protection is activated by Sensor Fail as well.
6.4 Date/Time
Time Stamp Per
[min]
Time interval for periodic history records.
Step: 1 min
Range: 0 – 200min
SummerTimeMod
[DISABLED/WINTER/SUMMER,WINTER-S, SUMER-S]
DISABLED: Automatic switching between summer and wintertime is disabled.
WINTER/SUMMER: Automatic switching between summer and wintertime is enabled and it is set to
winter/summer season.
WINTER-S/SUMMER-S: Modification for southern hemisphere.
Time
[HHMMSS]
Actual real time.
Date
[DDMMYYYY]
Actual date.
Timer1/2 Function
[No Func/TEST/TEST OnLd/MFail Blk/Mode OFF]
It is possible to choose out of 3 following Timer functions. Binary output Exerc Timer X is always
activated when Timer is active regardless of chosen Timer function. Timer functions require controller
running in AUT mode.
No Func:
There is no any other function, but the binary output Timer1 to 2 activation.
Auto Run:
When this option is chosen, the Timer output is also internally connected to the
Remote start binary input.
Mode OFF:
When this option is chosen, the Timer output is also internally connected to the
Remote OFF binary input.
Summary of Contents for 10 GSC
Page 2: ...1 Rev 3...
Page 57: ...U_ 3002_EN Rev 2...
Page 58: ...1 Rev 2...
Page 71: ...14 4 1 5 History log...
Page 99: ...42...
Page 100: ...43 Rev 2 U_ 3002_EN Rev 2...
Page 101: ...7 2 Genset Dimensions...
Page 104: ......
Page 105: ...7 3 Alternator s Connections...
Page 106: ......
Page 107: ......
Page 108: ...7 4 Regulator s Connections...
Page 109: ......
Page 110: ......
Page 111: ...7 5 Electrical Wiring Drawings...
Page 116: ...7 6 Tightening Torques...
Page 118: ...7 7 Instructions for decommissioning scrapping and disposal...