36
GENSET INCLINATION
DIMENSION D
(11 GTC / 14 GTAC /
10 GSC / 12 GSAC)
(17 GTC / 20 GTAC /
14 GSC / 17 GSAC)
4º
7,6 mm
3 mm
8º
14 mm
6,3 mm
12º
21,5 mm
8,7 mm
16º
28,7 mm
9,5 mm
20º
37,2 mm
13 mm
Table 11. Modification of oil dipstick for inclined operation
11 GTC / 14 GTAC / 10 GSC / 12 GSAC / 17 GTC / 20 GTAC / 14 GSC / 17 GSAC
Fig. 24. Modification of oil dipstick for inclined operation
NOTICE
Do not operate the genset if the oil level is below the Min mark or above the Max mark.
Be careful the oil dipstick marks refer to the genset as a horizontal position. Therefore, check
the genset inclination when the oil level is verified.
MAINTENANCE TASK. OIL FILL / CHANGE
Oil must be changed with hot genset so as to be sure the oil is fully drained. The procedure is
the following:
1.
Drain the oil (follow steps below)
a.
Stop the genset.
b.
Disconnect the battery negative (-) terminal.
c.
Remove the oil drain plug.
d.
Connect the external oil pump to the end of the oil drain hose. Place the
outlet of the pump into an oil collection container.
e.
Allow time for the engine oil to drain completely.
2.
Replace the oil filter.
3.
Fill with oil according to oil capacity circuit.
4.
Check for leaks.
5.
Check oil level according to the oil level check procedure.
Summary of Contents for 10 GSC
Page 2: ...1 Rev 3...
Page 57: ...U_ 3002_EN Rev 2...
Page 58: ...1 Rev 2...
Page 71: ...14 4 1 5 History log...
Page 99: ...42...
Page 100: ...43 Rev 2 U_ 3002_EN Rev 2...
Page 101: ...7 2 Genset Dimensions...
Page 104: ......
Page 105: ...7 3 Alternator s Connections...
Page 106: ......
Page 107: ......
Page 108: ...7 4 Regulator s Connections...
Page 109: ......
Page 110: ......
Page 111: ...7 5 Electrical Wiring Drawings...
Page 116: ...7 6 Tightening Torques...
Page 118: ...7 7 Instructions for decommissioning scrapping and disposal...