Bit
Location
Error Message
Cause and Troubleshooting
and check for internet connection. If internet
access is unavailable, contact your IT admin or
your internet provider.
5th
Server x Ping Failed
Ping or connection to SolarEdge server failed.
Check the SolarEdge server address, under
LAN
Conf
submenu:
Address: prod.solaredge.com
Port: 22222
Check with your network administrator whether
a firewall or another device is blocking
transmission.
6th
7th
8th
Tcp Connect. Failed
Meter Troubleshooting
For troubleshooting a built-in meter, refer to
http://www.solaredge.com/files/pdfs/built-in_rgm_
.
When a meter is connected, there will be a status screen for each meter function. The following is an
example of the export meter function status:
P r o d u c t i o n M e t e r
S t a t u s : < O K / E r r o r >
P o w e r [ W ] : x x x x x . x
E n e r g y [ W h ] : x x x x x . x
<OK> is not displayed
If
<OK>
is not displayed in the Status line of the status screens, the meter is not communicating with the
inverter communication board. Check the following:
l
There are no loose connections at the inverter communication board and at the meter.
l
The wiring between the 4-pin terminal block on the meter and the RS485 terminal block on the
Connection Unit is correct (refer to ).
An error message is displayed
If error code
3x6E
(or
Error 185
)
- Meter Comm. Error
is displayed in the meter status screen, verify
proper connection of:
l
The RS485 cables and connectors
l
The AC connection of the meter
Power [Wh] Import value is not advancing
If the inverter is not producing power, and there is power consumption by the loads, check the
following:
l
The meter status LEDs are lit. If the LEDs are all OFF, the meter is not connected to a power source.
o
Check the meter AC connection (10-pin terminal block)
o
Check that the meter breaker is ON
l
There are no loose connections at the 10-pin AC wiring of the meter.
l
The CT black and white cables are correctly connected to the 6-pin connector on the meter:
SolarEdge
-
StorEdge Installation Guide MAN-01-00262-1.3
94
Meter Troubleshooting