To verify the connection:
1. Press the inverter external LCD light button to display the status screens one after the other:
a. Check the RS485 communication status:
w w w w w w w w
D e v P r o t # #
R S 4 8 5 - 1 < M L T > < 0 2 > < 0 2 >
l
The
MLT
under
Dev
denotes that the configuration is for multiple devices.
l
The number under
Prot
(protocol) should display the number of
configured
devices.
l
The number under ## should display the number of
detected
devices.
The above screen shows an example of 2 devices on the same bus (for example: meter and
battery). If RGM is pre-installed, and a battery and an external meter are also installed, the screen
should show <3><3>.
If the number of devices under Prot does not match the number under ##, refer to
b. Check the meter(s): In the meter(s) status screen check that the status is
OK
. The following is an
example of the status of an Export (or Import) meter:
E x p o r t M e t e r
S t a t u s : < O K / E r r o r # >
P o w e r [ W ] : x x x x x . x
E n e r g y [ W h ] : X X X X X . X
If
Comm. Error
c. Check the battery information: identification, charging status and power, and the operating
mode.
B S N : X X X X X X X X X I D : 1 5
S O E : 8 9 %
W W W W
P W R : 2 W
T o t a l : < x > W h
S t a t e : C h a r g i n g
If
Comm. Error
Chapter 10: System Configuration