Problem
Description or possible cause
Troubleshooting
No power to the backup loads
while grid is OFF (power outage)
The backed-up loads are not
backed up
o
Check that the inverter is producing
power
o
Check that the Backup function is
enabled (
Backup conf
è
Backup
è
Enable
).
o
Check that there are no errors on
the inverter LCD
o
Check the circuit breakers on the
backed-up loads AC panel
o
Check that the AC breaker in the
Connection Unit are in the UP
position (see
)
o
Check that the AC bypass switch
in the Connection Unit is set to
position 1 (see
) .
Inverter without auto-transformer
(On-grid only) - The inverter does
not start production and
Error 182
Auto-Transformer Temp. Too
High
is displayed
The thermal sensor cables are not
connected.
Move the DIP switch SW2 in the
Connection Unit to the UP position
(ON) (refer to
A battery internal fault is displayed
on the LCD:
Battery Internal
Fault XXXX (ID: XX)
Fault # –according to battery
model. ID – battery's Modbus ID.
Contact SolarEdge Support
Appendix A: Troubleshooting
SolarEdge
-
StorEdge Installation Guide MAN-01-00262-1.3
99