PSS-G/RAID Alternative Energy System Deployment Guide
August 2020
|
Solar Stik
®
Inc.
102
|
PRO-Verter Historical Data Collection
The PRO-Verters can provide some historical data for generator and battery operation and fault
history.
Press the METER button on the PRO-Verter Controller to access both the BMK and AGS functions.
Scroll through 01 DC Meters, 02 AC Meters, 03 Timers until 04 AGS Meters or 05 BMK Meters is
displayed. AGS and BMK Meters represent the only data sets for the generator or the battery system
that is cumulative. The DC and AC meters indicate current status information only.
Status
01 DC Meters
METER
press
Top line shows inverter/
charger status
Bottom line shows current
menu heading
Press to
select meters
Rotate to
desired
selection:
Status
01 DC Meters
Status
02 AC Meters
Status
04 AGS Meters
Status
05 BMK Meters
Status
03 Timers
Auto Generator Start/Stop (AGS) Data
Gen Run Time
This menu displays the time the generator has been running since the AGS circuit auto started the
generator. This menu does not display run time when the generator has been manually started.
This hour meter resets each time the generator is stopped. This meter is useful when trying to
determine how long the generator has been running in the auto mode. This meter does not replace
the hour meter for total hours the generator has run.
AGS Temp
This feature is not enabled.
Days Since Gen Run
This menu displays the number of days since the generator has last run. This menu is useful in
determining if the AGS start and stop settings are set up correctly.
Note:
This meter resets whenever the generator is either auto started, exercised, or manually
started. The meter reads the B+ signal provided by the generator to the AGS module for this
meter.
Days Since 100% SOC
This read-only menu displays the number of days since the battery was at 100% SOC.