8.8. List of fuses
CAUTION!
When replacing fuses, only use fuses of type and size indicated in the present manual.
The accessible fuses used in the unit are listed in the table below, some fuses may not be present if the related optional
component is not installed in the unit (see
List of dedicated components
for more details about optional parts).
Fuse id.
q.ty
Fuse type
Function
F3
1
10x38 CC
5A
AC 230V
RCD
F6
2
10x38 CC
2A
1000V DC
U-Adapter
F7
1
10x38 CC
6A
AC 230V
Heater 1kW
F8A
F8B
2
10x38 CC
2A
AC 230V
Fan Extractor
F9
1
10x38 CC
1A
AC 230V
PCS Opt. Digiware
F10
3
10x38 CC
25A
AC 230V
AUX Mains
F11
1
10x38 CC
2A
AC 230V
Grid Code Board
F12
1
10x38 CC
1A
AC 230V
Control Box power supply
F17
1
10x38 CC
5A
AC 230V
Service Socket
F18A
F18B
2
10x38 CC
6A
AC 230V
Door Heaters
F19
1
10x38 CC
12A
AC 230V
Heaters 2kW
F20A
…
F20F
12
10x38 CC
20A
AC 230V
B-CAB 1
…
B-CAB 6
F21A
F21B
F21C
6
10x38 CC
1A
AC 230V
B-CAB 1-4
B-CAB 2-5
B-CAB 3-6
F22
1
10x38 CC
8A
AC 230V
UPS Input
F23
1
10x38 CC
6A
AC 230V
Automation box
F24
1
10x38 CC
8A
AC 230V
External UPS
F25
1
10x38 CC
1A
AC 230V
Heaters control relays
F26
1
10x38 CC
1A
AC 230V
Hyg Thermostat
The fuses are located in the areas indicated below:
These fuses can only be accessed by Socomec trained
personal.
Apart from the listed fuses, there are fuses to protecting the AC
mains and the DC line; only trained personal from Socomec is
authorized to replace these fuses.
The optional “SPD DC” are protected with a couple of fuses
located under the DC input bars.
Only trained personal from Socomec is authorized to replace
these fuses.
Figure 67. Location of the fuses inside the C-Cab