SUNSYS HES L - 551697A - SOCOMEC
68
EN
8.4.4.3. Connections of automation box
The Automation Box, may contain different optional components as listed in the “List of Options” section.
Below there is a list of the connectors present in the front of the Automation Box.
Refer to Socomec for additional details about the functions supported by the installed options.
Connector ID
Connector type
Pin number
Function
Eth 1
RJ45
External control
Eth 2
RJ45
PMS external
Eth 3
RJ45
C-CAB external
Eth 4
RJ45
Plant external
Eth 5
RJ45
Service – SAT
Eth 6 – Eth 9
RJ45
Free
Eth 10
RJ45
Communication with Control Box
X2
DB-9
CAN for B-CAB
X3
10 pin plug-in connector
1-2
Emergency stop input 1
3-4
Emergency stop input 2
5-6
Internal use
7-8
Internal use
9-10
Internal use
X4
10 pin plug-in connector
1-2
Emergency stop output
3-4
Emergency stop output
5-6
Emergency stop output
7-8
Emergency stop output
9-10
Emergency stop output
X5
10 pin plug-in connector
1-2
Input IX1.1 – reserved for PMS functionalities
3-4
Input IX1.2 – reserved for PMS functionalities
5-6
Input IX1.3 – reserved for PMS functionalities
7-8
Input IX1.4 – reserved for PMS functionalities
9-10
Input IX1.5 – reserved for PMS functionalities
X6
10 pin plug-in connector
1-2
Output QX1.0 – reserved for FSS (Battery Fire Safety
System alarm report) functionalities
3-4
Output QX1.1 – reserved for PMS functionalities
5-6
Output QX1.2 – reserved for PMS functionalities
7-8
Output QX1.3 – reserved for PMS functionalities
9-10
Output QX1.4 – reserved for PMS functionalities
X7
6 pin plug-in connector
1 - 6
Reserved
X8
3 pin plug-in connector
1
+
RS485 bus for “Digiware package for
PMS” and “Diris Aux power supply
measurement”
2
-
3
Shield
X9
3 pin plug-in connector
1
+
2
-
3
Shield
X10
3 pin plug-in connector
1
+
2
-
Shield
USB
USB
USB port for datalogger - Service only
Antenna
Proprietary device
Connection of antenna for “Wireless 4G modem”