SUNSYS HES L - 551697A - SOCOMEC
65
EN
AC aux from user’s UPS
The X107 terminal is used to supply the control circuit of the C-Cab.
X108 is the output of the internal UPS. It is possible to supply the control circuits with a separated line using the X107 input.
Note: none of the configurations addressed in this chapter replace the power supply connection to the X40 terminals
previously described, which is always required and necessary.
Connector
Pin
Function
Description
X107
1
L
AC optional auxiliary voltage
88÷132 V 1 ph+N 50/60 Hz
2
N
3
X108
1
L
Internal UPS output
120 V 60 Hz
2
N
X109
1
L
Not used
2
N
The pin 1 is the one indicated in the figure below:
For connection of plug-in connectors use cables in the following range:
1.5mm
2
÷2.5mm
2
/ 16÷12 AWG
Standard configuration
Aux from user’s UPS configuration