The following items are shipped with the B-Cab rack:
1. MSD
4 pieces of MSD are delivered and their installation must be
conducted after the fixation of the cables.
Figure 17. MSD
4.3. Storage
Store the cabinets in a dry and clean location protected from the elements and ensure that the ventilation openings
remain covered to prevent the entry of moisture or dust. No harmful gases, flammable or explosive products and corrosive
chemicals are allowed in the battery warehouse. The recommended storage temperature is about 20°C +/- 3°C with a daily
average storage temperature ≤25°C to preserve the life of the battery and limit its self-discharge, though the allowed range
of temperature is -20°C (-4°F) to +60°C (+15°F).
For storage duration exceding 1 month, please contact Socomec.
4.4. Handling and Moving
WARNING!
The packaging guarantees the stability of the unit during shipping and physical transfer.
The unit must remain in a vertical position during all shipping and handling operations.
Ensure that the floor is strong enough to support the weight of the unit.
Carry the packaged unit as close as possible to the installation site.
WARNING!
Move the unit using a fork lift truck taking the utmost caution at all times.
At least two people must handle the unit. The people MUST take position at the sides of the cabinet with respect
to the direction of movement.
Do not move the unit by putting pressure on the front door nor back plate.
When moving the unit on even slightly sloping surfaces, use the locking equipment and braking devices to ensure
that the unit does not fall over.
WARNING!
Provide vertical support while moving the unit due to its height and relatively high centre of gravity; move slowly
with care to avoid tipping.
C-Cab and B-Cab are shipped individually mounted on individual pallets.
If you need to transport through a building the minimum opening, with the roof installed, must be 1050mm x 2170mm for
the C-Cab and 1350mm x 2330mm for the B-Cab.