SUNSYS HES L - 551697A - SOCOMEC
34
EN
5.2.2.
Connection prerequisite
Grounding
1.
Any conductive battery racks, cases or trays must be connected to an equipment grounding conductor.
2.
Equipment grounding conductor is properly identified as either bare, green, or green with continuous yellow stripe(s)
4.
Check the ground interconnection of all the B-Cabinets.
5.
Check ground connection on the C-Cabinet.
Interconnection / Electrical cable visual inspection
1.
For all the system verify the connection (power and communication) of each cable is in accordance with the cable book, the single line
diagram and the installation manual provided by SOCOMEC.
2.
Check the Emergency Stop loop connection.
3.
Please provide a photo of the AC Cable connection od the C-Cabinet.
4.
Please provide a photo of the Auxiliaries Cable connection od the C-Cabinet.
5.
Please provide a photo of the DC and auxiliaries Cable connection od the B-Cabinet.
6.
"For Islanding.
Check all connection with devices required by SOCOMEC."
Sensors
1.
Check the connection of the Load sensor for CRD function to the C-cabinet.
Internet Connection (if no Modem 4G option)
1.
Check the internet connection wiring from your site to the C-Cabinet.
5.2.3.
IoT prerequisite
IP addresses for communication
1.
Please provide an IP address to communicate with the PMS (Power Management System).
2.
Please provide an IP address to communicate with the M70 (Measurement Central device).
3.
Please provide IP address range that will authorized to have access to the ESS data.
4.
Check ground connection on the C-Cabinet.
Network access (if no Modem 4G option)
1.
Please provide the network IP address.
2.
Please provide subnet mask.