GB
This symbol indicates that the product must not be thrown away with other household rub-
bish, so as not to harm the environment or human health (directive 2002/96/EC - WEEE).
See Socomec general terms & conditions of sale for more information on how to dispose
of this product.
CHARACTERISTICS
Available on the display
Active Energy
Consumed (+)
Total
Yes (kWh) tariff T1/T2/T3/T4
Total T = T1+T2+T3+T4 (kWh)
Partial
No
Produced (-)
Total
No
Partial
No
Reactive Energy
Consumed (+)
Total
Yes*
Partial
No
Produced (-)
Total
No*
Partial
No
Active Power
Instantaneous (P+)
Total
Yes* (kW)
Reactive Power
Instantaneous (P+)
Total
No*
COMMUNICATION
RS485
2 wires + shielding / half duplex
Protocol
JBUS/MODBUS®, RTU mode
Speed
4800 / 9600 / 19200 / 38400 Baud
Galvanic insulation
4 kV 1 min 50Hz
List of available functions
Cf. JBUS/MODBUS communication table
BACKUP
Energy registers
In non-volatile memory
Clock
On battery
Load curve*
In non-volatile memory
CLIMATE
Operating temperature
- 10°C to + 55°C
Storage temperature
- 20°C to + 70°C
Humidity
95% RH without condensation
CASE
Dimensions
Modular case 4 M wide (DIN 43880)
L x H x D (mm)
72 x 90 x 62.5
Mounting
On DIN rail
Connection capacity
Flexible: 1 to 6 mm² / Rigid: 1.5 to 10 mm²
Nominal tightening torque
1.5 N.m
Case type / insulation class
Isolating / II
Protection rating
To be installed under an IP65 box
Weight
240 g
OPTION
Terminal cover (sealing)
4850304U
RECYCLING
Substances involved
Lithium battery type CR2032 (non-replaceable welded battery)
Printed circuit
WEEE compliance
Yes - Directive relating to waste electrical and
electronic equipment
RoHS compliance
Yes - Restriction of the use of hazardous substances
List of displayed functions. Cf. table below.
55
COUNTIS E44R
Summary of Contents for COUNTIS E44R
Page 21: ...21 COUNTIS E44R Fig 1 Fig 2...
Page 23: ...Fig 1 Fig 2 23 COUNTIS E44R...
Page 25: ...Fig 1 Fig 2 25 COUNTIS E44R...
Page 27: ...Fig 1 Fig 2 27 COUNTIS E44R...
Page 66: ...66 COUNTIS E44R Ref 538 700 A...
Page 67: ...67 COUNTIS E44R...