- 56 -
No.
Phenomenon
Cause
Countermeasure
1)Contacts the stroke end of the
actuator or the workpiece.
Check the stroke position and how
workpieces are mounted.
Cannot be actuated manually
or by manual override
adjustment screw (does not
operate).
(At stop(EMG) or
SVRE[OFF])
2) [Lock type] is selected
Supply 24VDC power supply to the
[BK RLS] terminal of controller/CN1
power supply plug in order to unlock.
/see 5.6 Precautions for the actuator
with lock
Warning(7) on p.40
1) Load exceeding the maximum
work load is mounted, or
external force more than the
lock holding force is applied.
Check the mounted load and lock
holding force to confirm if they are
within the operation range.
/See 2.1 Specifications on p.9-12
7
Lock type is selected, but
workpieces are dropped during
stopping(EMG) or SVRE[OFF], or
moved by external force.
2) 24VDC is supplied to "BK RLS"
terminal of
controller/CN1 power supply
connector.
Stop supplying 24VDC power
supply to the [BK RLS] terminal
/see 5.6 Precautions for the actuator
with lock
Warning(8) on p.40