- 50 -
No.
Phenomenon
Cause
Countermeasure
1) The Power supply does not have
sufficient capacity.
Check the power consumption for
each actuator and controller:
If necessary replace the existing
power supply with a power supply
with sufficient capacity.
/See 2.1 Specifications on p.9-12
2) Load/resistance more than
spe
cified
range is being applied to
the actuator.
Use within specification range.
/See 2.1 Specifications on p.9-12
3) Pushing operation is
preformed with
“Positioning operation”
Review the content of the step
data.
/See 3.3 Step data setting on p.20-30
4) For the “pushing operation”,
the position (target
start-pushing position) is not
set correctly.
Check the step data.
/See 3.3 Step data setting on p.20-30
5) Breaking of belt
Please check the belt.
/See 6.4 Replacement of belt on
p.46
6) The cable is not connected
or has been disconnected.
Confirm that the cable is
connected correctly.
/See 4. Wiring of cable on p.35
7) It was not the intended origin
position because the actuator
pinched the work-piece during
the“return to origin”.
Remove the work-piece and
restart the return to the intended
origin position.
8) Wrong input [0] is input as the
positioning force.
Check the step data.
<
Moving force>
/See 3.3 Step data setting on p.20-30
9) The step data position is not
changed correctly after the
return to origin direction is
changed.
Check the step data.
<Position>
/See 3.3 Step data setting on p.20-30
2 Operation
not
completed
/ Operation continue
“Posn failed/code: 1-149” is
generated.
↓
<Procedure of restart>
Controller version /SV1.0 or later
1. Input the “reset signal.”
“SVRE”: Automatically ON
Controller version /SV0.6* or before
1. Input the “reset signal.”
“SVRE”: Automatically ON
2. Input the “setup signal.”
Restart operation after the
completion of the”retun to
origin”.
10) Because the operation of the
step data is set to [INC/relative],
the table comes into contact with
an external object and does not
move due to continuous
operation.
(Stroke end etc.)
Check the step data.
<Position>
/See 3.3 Step data setting on p.20-30
Label position
for controller version
Position : Bottom
SV1.0*