- 33 -
Alarm
Description
(code)
Teaching
box
Description
Gr
ou
p
Alarm
Clear
method
Condition / Countermeasure
Alarm_Com
ment_104
(1-104)
Battery is not
connected
C
Input
RESET
<Condition>
Battery is not connected to the controller
<Countermeasure>
Check the connection of the battery
Caution
Absolute ID not match (Initial condition) alarm is generated
before this alarm.
Alarm_Com
ment_105
(1-105)
Battery
temperature
rise
C
Input
RESET
<Condition>
The alarm is generated when the battery
temperature is too high.
<Countermeasure>
Adjust the ambient temperature of the controller.
Alarm_Com
ment_106
(1-106)
Absolute
communicati
on failure
C
Input
RESET
<Condition>
The alarm is generated when the communication
between the controller circuit and the absolute circuit is not
normal.
<Countermeasure>
Check the operating environment if there
is affect of noise.
Alarm_Com
ment_107
(1-107)
Battery
voltage
reduce
C
Input
RESET
<Condition>
The alarm is generated when the battery voltage
drops.
<Countermeasure>
Check if the setting of the period switch
is set correctly.
If the alarm reoccurs even after supplying power for 72
consecutive hours, replace the battery.
Caution
Absolute ID not match (Initial condition) alarm is generated
before this alarm, or abnormal absolute alarm is generated
simultaneously.
Motor
rotation
exceeds the
set value
(1-144)
Excessive
speed
D
RESET
Input
SVON
<Condition>
The motor speed exceeds a specific level due to
an external force, etc.
<Countermeasure>
Make improvements such that the motor
speed will not exceed the maximum speed of the actuator.
Caution
Please refer to the manual or the catalogue of the actuator for
the maximum speed of the actuator.