HRX-OM-R026
Chapter 3 Transport and Setting Up
3.4
Piping
HRSH Series
3-28
Recommended piping circuit
Fig. 3-20 Recommended piping circuit
No.
Description
Size
Recommended part no.
Note
1
Valve
Rc1/2
-
-
2
Valve
Rc1
-
-
Y-strainer
Rc1
#40
Accessory
Filter
Rc1
20μm
HRS-PF005
Note)
4
Flow meter
-
-
Prepare a flow meter with an appropriate flow
range.
5
Valve
(Part of thermo-chiller)
Rc1/4
-
-
6
Pressure gauge
0~1.0MPa
-
-
Y-strainer
Rc1/2
#40
-
Filter
Rc1/2
20μm
-
8
Valve
Rc3/8
-
-
Y-strainer
Rc3/8
#40
-
Filter
Rc3/8
20μm
FQ1011N-10-T020-B-X61
Note)
Note) The filter shown above cannot be directly connected to the thermo-chiller. Install it in the user’s piping system.
3
Install either the strainer or filter. If foreign objects
with a size of 20 μm or more are likely to enter,
install the particle filter.
7
Install either the strainer or filter. If foreign objects
with a size of 20 μm or more are likely to enter,
install the particle filter.
9
Install either the strainer or filter. If foreign objects
with a size of 20 μm or more are likely to enter,
install the particle filter.